background image

OS-1933-E3-003

OS System Configuration

3-2

044-05243 Rev A

OS System Configuration

Configure PC for Communication

Powerwave products typically have two LAN connections for interfacing with the customer’s equipment for
control and monitoring of the product, see Figure 3-1.    The “Site LAN” is used to interface with the customer’s
base station (BTS) equipment for remote control and monitoring and the “Local LAN” is used for walk up or
local control and monitoring.   The Site LAN IP address is assigned automatically by DHCP. The Local LAN IP
address is fixed from the factory at 192.168.255.1. To communicate with the product via the Local LAN, the
user must configure the laptop with a fixed IP address such as “192.168.255.2”.
There are several ways to access the Network Connections dialog box and may be different from operating
system to operating system. The following steps in Table 3-2 and Figures 3-1 through 3-6 are based on using
Windows XP.

The PC’s network interface should now be ready to communicate through the Local LAN.

8

Measure the output DC voltage. There is a fused output for each MCPA and the Controller. All 

outputs should be 28.5V +/-0.5Vdc. If the voltage measurements are non-compliant with the 

limits troubleshoot the power system before proceeding.

9

Close and secure the rear door to ensure the rear fan will operate

10

Enable all of the installed MCPAs. After ~10seconds the MCPAs should display a solid green 

LED. If not a solid green reference the troubleshooting section in Chapter 4.

11

The LEDs on the front panel of the controller will illuminate solid green for the enabled and 

functioning sectors. Alarms may be present; the configuration portion of the installation should 

be performed.

Table 3-2  Configure PC for Communication

Step

Action

1

Connect a laptop PC to the front Ethernet port on the control module with a network cross-

over cable. See Figure 3-1.

2

Go to Network Connections through either the Control Panel, the Start Menu, or by clicking 

the Network Connections icon in the system tray. See Figure 3-2.

3

Right click and select “disable” for the “Local Area Connection” or appropriate network 

connection that will be connected to the Local LAN.

4

Right click and select “properties” to bring up the “Properties” dialog box. See Figure 3-3.

5

In the “This connection uses the following items:” field, deselect all checkboxes except the 

Internet Protocol (TCP/IP) checkbox. See Figure 3-3

6

Highlight the “Internet Protocol (TCP/IP)” menu item and select Properties to bring up the 

“Internet Protocol (TCP/IP) Properties” dialog box. See Figure 3-4.

7

Check “Use the following IP address” and enter the fixed IP address such as 

“192.168.255.2.” Enter the Subnet mask of 255.255.255.0. See Figure 3-5.

8

Select “OK” and then “Close.” 

9

Right click on the network connection and select “Enable.” See Figure 3-6.

10

Open a web browser and type in the following web page - http://192.168.0.1.8080.

11

Type in ” User” as the User ID and “Password” for the Password.

12

Choose Submit.

Table 3-1  Initial Start-Up Procedure (Continued)

Summary of Contents for OS-1933-E0-003

Page 1: ...044 05243 Rev A June 2008 O U T D O O R B O O S T E R S Y S T E M I N S T A L L A T I O N A N D S E R V I C E M A N U A L OS MCPA OUTDOOR SYSTEM OS 1933 E0 003 Installation and...

Page 2: ...in this document may cause 1 Spurious emissions that violate regulatory requirements 2 The equipment to be automatically removed from service when maximum thresholds are exceeded 3 The equipment to no...

Page 3: ...OS 1933 E3 003 Revision Record 044 05243 Rev A i Revision Record Revision Date of Change Reason for Change Rev A June 2008 Initial Release...

Page 4: ...OS 1933 E3 003 Revision Record ii 044 05243 Rev A This page intentionally left blank...

Page 5: ...tial exists for equipment damage or loss of data NOTE Notes contain helpful suggestions or references to material not covered in the document Safety Any personnel involved in installation operation or...

Page 6: ...Safety OS 1933 E3 003 viii 044 05243 Rev A This page intentionally left blank...

Page 7: ...nstallation Instructions 2 2 AC Power 2 3 RF Cable 2 4 Form C Alarms 2 6 External Alarms EA 2 7 MCPA 2 7 Power system Installation 2 9 RFCU Installation 2 9 Chapter 3 Operation Introduction 3 1 Initia...

Page 8: ...arm Inputs 3 18 Chapter 4 Maintenance Introduction 4 1 Periodic Maintenance 4 1 Cleaning Air Inlets Outlets Filter 4 1 Troubleshooting 4 2 MCPA does not have a solid green LED 4 2 Rectifier Module wit...

Page 9: ...alog Box 3 4 3 4 Internet Protocol TCP IP Properties 3 4 3 5 Setting the IP Address 3 5 3 6 Enable the Connection 3 5 3 7 Rectifier Front Panel 3 8 3 8 MCPA Front Panel 3 9 3 9 Controller Module 3 10...

Page 10: ...ifier Modules 3 6 3 5 Activate TMA Channels 3 6 3 6 Adjust LNA Gain 3 7 3 7 Adjust Tx Gain 3 7 3 8 Adjust VSWR Alarm 3 7 3 9 Activate External Alarm Inputs 3 7 3 10 Status Verification 3 8 3 11 Rectif...

Page 11: ...a secure fixed location RF connections are located on the interface bulkhead plate at the bottom rear of the cabinet External power communications and alarm cables are routed through access holes loca...

Page 12: ...air through a filter mounted in the front panel vents and send heated air out the filter mounted in the rear panel The variable speed fans are dependant on the MCPA power system Controller Module tem...

Page 13: ...dule Display X Form C Fan XX Fault FT front RT frear Minor RFCU Fault 3 Sector 1 3 Critical Bypassx DC Fault 3 Sector 1 3 Critical LNA 1 Fault LNA 2 Fault Sector 1 3 Major 1 Rect Comm Fault Minor Rect...

Page 14: ...nuator Section RFCU_Sector_2 SECTOR_0 RF Interface SECTOR_1 RF Interface SECTOR_2 RF Interface BTS TX3 BTS TX4 BTS TX1 RXm BTS TX2 RXd ANT RXd ANT TX RXm VSWR BTS TX3 BTS TX4 BTS TX1 RXm BTS TX2 RXd A...

Page 15: ...n Figure 1 4 Outdoor System Rear View Door Open Power System MCPAs Controller Module Intrusion Alarm Switch Fan RF Conditioning Unit s Rectifier Modules RF Input and Output Interface Ground Power Alar...

Page 16: ...OS 1933 E3 003 Scope of Manual 1 6 044 05243 Rev A Figure 1 5 MCPA Figure 1 6 RF Conditioning Unit Figure 1 7 Control Module Front Panel Front Rear Rear Front...

Page 17: ...Scope of Manual OS 1933 E3 003 044 05243 Rev A 1 7 Figure 1 8 Power System Rectifier 0 Rectifier 1 Rectifier 2 Rectifier 3...

Page 18: ...OS 1933 E3 003 Scope of Manual 1 8 044 05243 Rev A This page intentionally left blank...

Page 19: ...factory for a return material authorization RMA Refer to Chapter 4 Electrical Service Recommendations The base station AC supply to each OS should have a single phase UL listed AC circuit breaker rate...

Page 20: ...d on the left side facing unit to allow for door swing Recommended minimum clearances for the front of the cabinet is 36 inches and 20 inches for the rear of the cabinet Refer to Tables 2 3 and 2 4 re...

Page 21: ...es Digital volt ohm meter Verify voltage Roto hammer Mounting unistrut or cabinet 10 mm hex socket wrench or nut driver Open door latches Drill bit Mounting unistrut or cabinet Screwdriver slotted 5 m...

Page 22: ...rements detailed in Chapter 5 CAUTION Prior to connecting BTS cables verify booster system power is off NOTE Do not install weatherproofing materials to cables until the booster commissioning is compl...

Page 23: ...allation Instructions OS 1933 E3 003 044 05243 Rev A 2 5 Figure 2 2 Interface Bulkhead RFCU Connections Figure 2 3 Controller Module Installation Ground Studs M8 Studs 3 4 19 mm Control Module Thumbsc...

Page 24: ...structed in Table 2 7 Alarm 1 Minor Any cabinet fan fault intrusion or rectifier communication fault The system requires attention Alarm 2 Major The system performance is degraded Alarm 3 Critical 1 S...

Page 25: ...y empty MCPA or RFCU slots before operation of the OS to prevent overheating and ensure proper system airflow Table 2 8 Form C Alarm Terminal Block Relay Connections and Conditions Relay Continuity Me...

Page 26: ...erify MCPA top and bottom quarter turn fasteners are in unlocked position as shown in Figure 2 5 4 Gently slide MCPA into subrack until seated Turn top and bottom quarter turn fasteners clockwise to s...

Page 27: ...brack may cause the pins on the D Sub connector to become recessed or broken Table 2 11 Rectifier Module Configurations Active sectors Max DC Power Number of Rectifier Modules Required Power System Ca...

Page 28: ...OS 1933 E3 003 Installation Instructions 2 10 044 05243 Rev A This page intentionally left blank...

Page 29: ...led at least one cabinet door must be closed and secured to provide adequate cooling All three OS system slots must be populated with an MCPA Rectifier or a blank panel to provide adequate cooling air...

Page 30: ...display a solid green LED If not a solid green reference the troubleshooting section in Chapter 4 11 The LEDs on the front panel of the controller will illuminate solid green for the enabled and funct...

Page 31: ...Controller Module Connections Figure 3 2 Network Connections Dialog Box Powerwave Product 192 168 255 1 Customer BTS Equipment Site LAN Local LAN Ethernet Laptop 192 168 255 2 Ethernet Typical product...

Page 32: ...OS 1933 E3 003 OS System Configuration 3 4 044 05243 Rev A Figure 3 3 Local Area Connection Properties Dialog Box Figure 3 4 Internet Protocol TCP IP Properties...

Page 33: ...3 Activate Sectors Step Action 1 Select the System Configuration Page See Figure 3 15 2 Using the pull down menus in the Installed section choose YES for the Sectors to be utilized The Sectors are 1 f...

Reviews: