background image

4. Installation of Air Heater(s)

4.1 General

Before installation, check that the local distribution 

conditions, nature of gas and pressure (or oil type), and 

adjustment of the appliance are compatible.

The air heater must be installed in accordance with the rules in 

force and the relevant requirements of any fire regulations or 

insurance company’s requirements appertaining to the area in 

which the heater is located, particularly where special risks are 

involved such as areas where petrol vehicles are housed, where 

cellulose spraying is carried out, in wood working departments 

etc.

The following minimum clearances for installation and servicing 

must be observed. 

To the front 

 

1.0m 

To the rear 

 

The depth of the heater

To the side 

 

1.0m 

Above the heater  

1.0m 

Any combustible material adjacent to the air heater and the flue 

system must be so placed or shielded as to ensure that its 

temperature does not exceed 65 °C.

IMPORTANT:

1.No air heater shall be installed where there is a foreseeable 

risk of flammable particles, gases vapours or corrosion inducing 

gases or vapours being drawn into either the heated air stream 

or the air for combustion. In such cases installation may only 

proceed if the air to be heated and the air for combustion are 

ducted to the heater from an uncontaminated source preferably 

outside the building. In certain situations where only airborne 

particles are present it may suffice to fit filters on the air inlet 

ducts of the heater. Advice in these instances may be obtained 

from Powrmatic Ltd.

4.2 Location

The location chosen for the air heater must permit:

-  the provision of a satisfactory flue system and an adequate air 

supply.

-  adequate space for servicing and air circulation around the air 

heater.

The heater(s) must not be installed in conditions for which it is 

not specifically designed e.g. where the atmosphere is corrosive 

or salty, and they are not suitable for outdoor use unless the /EA 

style is specified. /EA heaters must be installed on a plinth such 

that there is a minimum distance of 0.5m between ground level 

and the lowest point of any air inlet grilles.

Where the location of the air heater is such that it might suffer 

external mechanical damage e.g. from overhead cranes, fork 

lift trucks, it must be suitably protected. 

TE heaters are for normal operation within an ambient 

temperature range of -10 to 25°C.

4.3 Installation

TE heater installation may only be completed by Powrmatic 

Ltd or their appointed representatives.The heaters must be 

installed on a level noncombustible floor capable of supporting 

the weight of the heater.

4.4 Combustion & Ventilation Air Supply

There shall be provision for a supply of air for combustion. 

1) Installation in the heated space

In buildings with a design air change rate of 0.5 /h or greater, 

additional natural or mechanical ventilation is not necessary.

In buildings not having a design air change rate of 0.5 /h the 

following apply.

Natural Ventilation

Grilles having a free area of at least 2cm² per kW of rated heat 

input shall be provided at low level i.e. below the level of the 

heater flue connection.

Mechanical Ventilation

Must ensure that the space air change rate is at least 0.5/h, must 

be of the ‘input’ type and interlocked to ensure the heaters cannot 

work if the input system is not working.

2) Installation in plant rooms or enclosures

This type of installation is not applicable to TE heaters.

4.5 Flue System

A single wall tee piece is supplied with each heater and must 

be fitted to the flue outlet socket on the heater. A closed chimney 

system that conforms to the requirements of EN1856-1 and has 

a designation appropriate to the application must be connected 

to the outlet of this tee. The cross sectional area of the chimney 

serving the appliance must be not less than the area of the flue 

outlet of the air heater. The chimney must have a minimum 

height, from the heater to the flue terminal, of 2m. Horizontal 

runs  of  flue  must  be  minimised  but  where  they  are                    

unavoidable the ratio of vertical to horizontal flue should be 

not less than 3:1.

If necessary a single offset using two 45° bends can be included 

to avoid obstructions. The minimum equivalent resistance of 

the flue system should not be less than 0.0mb, the maximum 

not greater than 0.5mb. Details of how to calculate the resistance 

of the flue to be installed are given in Appendix A.

In order to minimise condensation the use of twin wall chimney 

is recommended. With high efficiency heaters some condensation 

in the chimney, particularly at the terminal, is unavoidable and 

in addition there can also be rain water ingress. Use of  a chimney 

system having joint seals will minimise any leakage from the 

flue system. The heater tee is provided with a collection tray 

and the outlet from this should be run to a drainage point e.g. 

a gully. The condensation pipe from the collection tray to the 

disposal point should be of non-corrodible material of not less 

than 22mm (3/4") size.

Facilities should be made for disconnecting the chimney pipe(s) 

from the air heater(s) for inspection and servicing purposes.

The chimney outlet must be fitted with a terminal and where 

the heater chimney is less than 200mm (8") in diameter an 

approved terminal must be used.

The chimney must be supported independently of the air heater.

The chimney must terminate in a freely exposed position and 

must be situated so as to prevent the products of combustion 

entering any opening in a building in such concentration as to 

be prejudicial to health or a nuisance..

  The chimney terminal must be installed not less than:

- 300mm below an opening e.g. window, air brick etc.

- 200mm below eaves or gutter.

- 300mm from an internal or external corner.

- 1200mm from a surface facing the terminal.

- 1500mm vertically from another terminal on the same wall.

- 300mm horizontally from another terminal on the same wall.

- 2000mm from ground level.

4.6 Fuel Connection

4.6.1 Gas Connection 

(if applicable)

A servicing valve and downstream union must be fitted at the 

inlet to the air heater gas controls assembly to facilitate servicing. 

The gas supply to the air heater must be completed in solid 

pipework and be adequately supported.

Warning

When completing the final gas connection to the heater do not 

place undue strain on the gas pipework of the heater.

4.6.2 Oil Connection 

(if applicable)

Refer to the supplied burner installation instructions for details 

regarding oil supply options.

5.4 Lighting the Air Heater

5.4.1 Gas Controls Assembly - Soundness 

Check

1. Ensure the gas service valve at the inlet to the gas controls 

assembly is shut.

2. To prove soundness of the first main safety shut-off 

valve and first start gas safety shut-off valve:- 

a)  Connect pressure gauge to the inlet pressure test point on  

 

the main valve block or inlet pipework.

b)  Open gas service valve and allow pressure to  

 

 stabilise before shutting it again. The valves are sound if  

 

no pressure drop is observerved. If a pressure drop is  

 

observed do not proceed until the fault has been rectified.  

 

Remove pressure gauge and refit sealing screw in pressure  

 

test point.

5.4.2 Sequence Check

1. Refer to the burner instructions supplied with the heater.

5.4.3 Final Adjustment

1. Remove the sealing screw from the pressure test point located 

on the side of the gas inlet to the burner head and attach a 

pressure gauge. Remove the sample point cover plug from the 

outlet flue length and insert a CO

measuring instrument.

2. Remove the link in the main electrical control panel to isolate 

the main gas valves.

3. Turn "ON" the main electricity supply and check that the 

following sequence of events occur.

i)  Burner fan runs.

ii)  Ignition spark is heard.

iii)  Start gas valves open.

iv)  Start gas flame is established.

4. Check that the start gas pressure agrees with that in Tables 

3.1 or 3.2. If necessary adjust the start gas pressure (See Data 

Sheet).

4. Turn "OFF" the main electricity supply.

5. Reconnect the main gas valves electrical link.

6. Turn "ON" the main electrical supply and the burner will run 

through its sequence untill main flame is established. Check 

that the main burner gas pressure agrees with that on the 

specification sheet. If necessary adjust the main burner gas 

pressure (See Data Sheet and also Burner Manual for method). 

7. Measure the CO

2

 content of the flue gases. If it is necessary 

to adjust the combustion air ratio controls, to obtain a reading 

of 9.0 - 9.5%, refer to the Burner Manual.

8. Remove pressure gauge, refit sealing screw in pressure test 

point and flue sample point cover plug.

 

 

5.4.4 Final Soundness Test

1. After making final gas rate checks all joints on the gas controls 

assembly must be tested for soundness using leak detection 

fluid.

5.5 Controls

The general layout of the control panel is as shown opposite. 

The MC200 controller is mounted in the access door of the 

electrical panel.

5.5.1 Inverter Drives

This will have been set prior to the heater being despatched. A 

data sheet of the settings used is included for future reference. 

5.5.3 MC200

See the MC200 instructions seperately supplied.

 

5.6 Hand Over

Hand the Users Instructions to the user or purchaser for retention 

and instruct in the efficient and safe operation of the air heater 

and associated controls.

Adjust the automatic controls to those values required by the 

User.

Finally, advise the user or purchaser that, for continued efficient 

and safe operation of the air heater, it is important that servicing 

is carried out annually.

In the event that the premises are not yet occupied turn off the 

gas and electricity supplies and leave instructional literature 

adjacent to gas meter.

10

6. Servicing

WARNING: Always switch off and disconnect electricity supply 

and close the gas service valve before carrying out any servicing 

work or replacement of failed components. Access doors on TE 

units are fitted with electrical interlocks however these alone 

must not be relied upon to prevent equipment operation during 

maintenace or servicing work.

6.1 General

Full maintenance should be undertaken not less than once per 

year. After any servicing work has been completed or any 

component replaced the air heater(s) must be fully commissioned 

and tested for soundness as described in Section 6.

6.2 Burner Maintenance

1. Refer to the Burner Instructions supplied with the heater.

6.3 Heat Exchanger Cleaning

1. Disconnect the gas supply at the inlet to the gas controls 

assembly.

2. Unplug  the electrical connections from the heater electrical 

panel to the buner.

3. Remove the nuts securing the burner to the heat exchanger 

and remove the burner.

4. (TE 41 & 61 only) Remove the fixings of  the second section 

(from the floor) rear panel and hinge panel down to expose the 

heat exchanger clean out access plate.

(TE21 only) Remove heater rear panel. 

5. Remove the nuts securing the cleanout plate and remove.

6. Withdraw the heat exchanger baffles, if fitted.

7. Brush through heat exchanger tubes and remove loose material 

using a vacuum cleaner.

8. Reassemble all components in reverse order. Inspect all gaskets 

and replace if necessary.

6.4 Fan Assembly

WARNING

 Electrical supplies to the heater must be isolated 

and

 locked OFF before proceeding.

1. Gain access to the fan section by removing the lower panels.

2. Inspect the fan blades to see that they are not damaged and 

that there is no excessive build up of deposits that could give 

rise to an imbalance. If necessary clean the fan blades using a 

stiff brush and vacuum cleaner.

6.5 Replacement of Faulty Components

6.5.1. Burner Components

1. Refer to the burner supplement supplied with the heater.

6.5.2  Gas Controls Assembly

1. Refer to the burner supplement supplied with the heater.

6.5.3 Main Fan Motors

DANGER

 Electrical supplies to the heater must be isolated 

and

 locked OFF before proceeding.

1. Remove fan assmbly from motor shaft. Note: On TE41 and 

TE61 units the fans are fitted to the motor shafts by taper lock 

bushes.

To remove a bush slacken all screws in it and remove (one or 

two screws depending on the size of the bush). After oiling point 

and thread of grub screws (bush size 1008 to 3030) or under 

the head and thread of cap screws (bush size 3535 to 5050) 

insert them into the jacking off hole(s) in the bush.

Tighten the screw(s) uniformly and alternatively until the bush 

is loose in the hub and fan is free on the motor shaft. Remove 

fan and bush.

4.6 Electrical Connections

Wiring external to the air heater must be installed in accordance 

with the I.E.E. Regulations for Electrical Installations and any 

local regulations which apply. Wiring should be completed in 

flexible conduit.

Heaters are for use with 230V, 1N, 50Hz or 400V, 3N, 50Hz 

supplies 

(see heater data plate)

.

The method of connection to the main electricity supply must:-

- facilitate the complete electrical isolation of the heater(s) that 

will prevent remote activation of the heater during servicing.

- be in a readily accessible position adjacent to the heater(s).

- serve only the heater(s).

- have a contact separation of at least 3mm in all poles. See the 

wiring diagram for the heater electrical connections. All units 

are fully pre-wired and only require final connections for the 

incoming mains supply.  The electrical supply must be run to a 

point adjacent to the heater and be suitably terminated to provide 

an isolation point that will prevent remote activation of the unit 

during servicing. The heater electrical panel is located at the 

front of the heater and cable entry points are provided in the 

adjacent heater framework. Reference must be made to the 

enclosed data sheet to ascertain the electrical loading of the air 

heater(s) being installed so that cables of adequate cross-sectional 

area to safely carry that load are used for the electrical 

installation. The length of the conductors between the cord 

anchorage and the terminals must be such that the current 

carrying conductors become taut before the earth conductor if 

the cable or cord slips out of the cord anchorage. All external 

controls must be of an approved type.

See the wiring diagram accompanying these instructions.

5. Commissioning & Testing

Note: TE41 & TE61 - Turn key for electical panel access door 

locks may be used to operate door elctrical interlock for 

commissioning purposes .

5.1 Electrical Installation

Checks to ensure electrical safety must be carried out by a 

qualified person.

5.2 Gas Installation

The whole of the gas installation, including the meter, should 

be inspected and tested for soundness and purged in accordance 

with the recommendations of the applicable IGE documents.

5.3 Fan Rotation

1. Whilst the main electrical supply is isolated and 

locked off

 

inspect the fan blades and ascertain the required direction of 

rotation. See below.

1. Reinstate the electrical supply Turn the AUTO-OFF-MAN 

switch to 'MAN'. Depending on the current state and setting of 

the MC200 the mains fans may start immediately. If they do 

not switch MC200 control (see MC200 manual supplied) to 

‘Summer’ mode and then press the fan button on the front cover.

2. Ensure that the fan direction of rotation corresponds with the 

direction of rotation arrow on the fan blades. If necessary turn 

the  AUTO-OFF-MAN switch to 'OFF', turn OFF the main 

isolator and reverse the direction of rotation by interchanging 

any two of the 3ph main supply leads at the terminal strip in the 

electrical panel. 

2. If appropriate reset the MC200 to Winter mode.

Fault

Main burner will not light

 

Main burner lights, but 

goes out before main fan 

comes on.

Main fan fails to run 

Cause

Electrical

Electrical

Electrical

Action

1. Check electrical and fuel supplies are ON. 

2. Check controls are ON or calling for heat.

1. Unit goes out on high limit -

a. Check limit thermostat setting - See Section  7.5.5. 

b. Faulty limit thermostat - change.

3. Inverter code 0C6, motor overloaded. - Check running amps. See 

specification sheet.

1. Fan motor (or capacitor - 1ph only) failed - replace.

2. Fan thermostat faulty - replace.

3. Inverter failed - replace 

     

8. Short List of Parts

Refer  to the burner supplement supplied with the heater.

Refer to Powrmatic Ltd for the details of other parts quoting the serial number of the heater.

7. 

Fault Finding

Refer also to the burner supplement supplied with the heater

3. Fit new motor and reassemble in reverse order.

Refit the taper lock bush into the fan and line up the holes (half 

threaded holes must line up with half straight holes). Lightly 

oil the grub screw or cap screws and srew in but do not tighten. 

Fit fan to shaft. Gradually tighten the grub/cap screws in 

accordance with the torque schedule. Fill all holes with grease 

to prevent dirt ingress. Recheck torque settings after half an 

hours running.

6.5.4 Main Air Fan(s)

DANGER

 Electrical supplies to the heater must be isolated 

and

 locked OFF before proceeding.

Should it be necessary to replace one or both of the fans 

proceed as follows.

(TE41 & 61) 

1. Remove fans as detailed in 6.5.3 above. On units with fans 

having a high number of blades it may also be necessary to 

remove one or two heat exchanger module side panels. 

(TE21 & 31)

1. Remove one or two side panels  to gain access to the top of 

the fan shaft. Remove set screw securing fan assembly to the 

motor shaft and remove fan.

2. Fit new fan(s) and reassemble in reverse order. Ensure  the 

loose key that prevents the fan assembly rotating on the fan 

shaft is refitted.

6.5.5 Fan and Limit Thermostats

 

6.5.5.1 Honeywell L4064B

1. Release the single screw securing the fan and limit thermostat 

cover and remove cover by pulling forward.

2. Release wiring from screw terminals.

3. Remove the 2 screws securing the thermostat to the heater 

panel and withdraw thermostat and sensor.

4. Reassemble new unit in reverse order refering to the heater 

wiring diagram to ensure correct wiring location.

Important:

 A replacement fan/limit thermostat will have a brass 

link between the bottom fan terminal and the bottom limit 

terminal (situated in the slot between the two terminals). This 

MUST

 be removed, by breaking the link off using a pair of thin

nose pliers, before the replacement thermostat is installed.

5. Ensure that the fan and limit settings are as follows:-

  Fan ON - 40°C, Fan OFF - 20°C

 Limit  60°C

Note:

  The new L4064B may be supplied with the limit 

temperature mechanically limited to less than the setting required. 

To release the mechanical limit push a pointed object into the 

small hole at the top of the dial. At the same time prevent the 

dial from rotating and push the limit temperature adjuster around 

to the required setting.

6.5.5.2 High Limit Thermostat

TE41 & 61

1. Release the two screws securing the limit thermostat housing 

cover and remove cover by pulling forward.

2. Release the thermostat from the front cover, two screws

3. Pull off wiring connectors from under the thermostat.

4.Remove a central side panel from the heater exchanger section 

to gain access to the heat exchanger and release the thermostat 

sensing phial from its holder on top of the heat exchanger and 

withdraw thermostat and phial.

5. Reassemble new unit in reverse order refering to the heater 

wiring diagram to ensure correct wiring location.

6. Ensure that the setting is as follows:-

 

Limit 100°C

TE21 & 31

1. Release the two screws securing the limit thermostat housing 

cover and remove cover by pulling forward.

2. Release the thermostat from the front cover, two screws

3. Pull off wiring connectors from under the thermostat.

4.Remove heater side panels  and release the thermostat sensing 

phial from its holder on  the fan shroud and withdraw thermostat 

and phial.

5. Reassemble new unit in reverse order refering to the heater 

wiring diagram to ensure correct wiring location.

6. Ensure that the setting is as follows:-

 

Limit 50°C

6.5.5.3 Fan Protection Thermostat

TE 21 & TE31

1. To replace the thermocouple remove the side panels on 

on side of the heater. Release the tip of the thermocouple 

from its holder and disconecct the other end from the relay 

base. Renew using a Type K thermocouple only.

2. Disconnect the electrical connections from the motor and 

remove the motor. Note: Providing the replacement motor is 

identical it is recommended that bolts are fitted in the motor 

mounting plate directly under the existing motor so that mounting 

position is marked. The bolts will also support the weight of the 

new motor whilst it is fitted.

Summary of Contents for TE21

Page 1: ...tallation Servicing Instructions Gas Oil Fired Heaters Direct Drive Fans WARNING THIS APPLIANCE MUST BE EARTHED CE TE Range Users Installation Servicing Instructions Issue 7 0 April 2014 The Powrmaster TE Range ...

Page 2: ... to Powrmatic 3 The heater has been maintained on a yearly basis by a competent servicing company 4 The heater has been used in accordance with the manufacturers instructions 5 The correct specification fuel has been used 6 No unauthorised repairs or modifications have been made 7 Powrmatic General Conditions of Sale have been observed 8 Except for the obligation of Powrmatic Ltd to perform warran...

Page 3: ...ill then fire NOTE If the burner fails to light it will go to lockout and the lockout indicator reset button on the burner control box will be illuminated To restart the burner push the lockout reset button If the unit will not light after two or three attempts then shut down the unit and call in a service engineer 3 To Shut Down the Air Heater 3 1 For Short Periods Set the MC200 to OFF See MC200 ...

Page 4: ...wrmatic heaters use gas or oil and electricity to power them they may also contain moving parts such as pulley belts It would be hazardous to tamper with or attempt to service unless you are a competent person in the field of Gas and Electrical work If you have any safety questions reference the servicing and installation of any of our heaters please do not hesitate to contact our head office for ...

Page 5: ...ously thereby constantly circulating the air in the building Each fan is directly mounted onto the drive motor shaft and the speed is governed by an inverter Heaters are fitted as standard with fully automatic monoblock On Off forced draught gas burners and monoblock gas control assemblies High Low or 3 CONTENTS Section Title Page 1 Introduction 3 2 Technical Data 4 3 General Requirements 5 4 Inst...

Page 6: ...el A B C D E F G mm 1010 1568 1873 in Total 1873 1416 150 mm 1162 2025 1213 1574 1778 660 200 mm 1518 2991 1213 1975 1899 959 300 350 mm 2026 4058 1721 2534 2432 1365 Specifications Burner Pressures and Electrical Data TE heaters are designed to suit individual applications Please refer to the enclosed specification sheet for the data specific to the heater supplied Note The number of extension mo...

Page 7: ...ut off switch at the booster inlet The local gas undertaking must be consulted before a gas pressure booster is fitted 3 2 Oil Fired Heaters 3 2 1 Related Documents The installation of the air heater s must be in accordance with the rules in force and the relevant requirements of the Building Regulations and the I E E Regulations for Electrical Installations It should also be in accordance with an...

Page 8: ...ical Ventilation Must ensure that the space air change rate is at least 0 5 h must be of the input type and interlocked to ensure the heaters cannot work if the input system is not working 2 Installation in plant rooms or enclosures This type of installation is not applicable to TE heaters 4 5 Flue System A single wall tee piece is supplied with each heater and must be fitted to the flue outlet so...

Page 9: ...ficient 4 6 Electrical Connections Wiring external to the air heater must be installed in accordance with the I E E Regulations for Electrical Installations and any local regulations which apply Wiring should be completed in flexible conduit Heaters are for use with 230V 1N 50Hz or 400V 3N 50Hz supplies see heater data plate The method of connection to the main electricity supply must facilitate t...

Page 10: ...r must be isolated and locked OFF before proceeding 1 Gain access to the fan section by removing the lower panels 2 Inspect the fan blades to see that they are not damaged and that there is no excessive build up of deposits that could give rise to an imbalance If necessary clean the fan blades using a stiff brush and vacuum cleaner 6 5 Replacement of Faulty Components 6 5 1 Burner Components 1 Ref...

Page 11: ...replacement fan limit thermostat will have a brass link between the bottom fan terminal and the bottom limit terminal situated in the slot between the two terminals This MUST be removed by breaking the link off using a pair of thin nose pliers before the replacement thermostat is installed 5 Ensure that the fan and limit settings are as follows Fan ON 40 C Fan OFF 20 C Limit 60 C Note The new L406...

Page 12: ...ostat setting See Section 7 5 5 b Faulty limit thermostat change 3 Inverter code 0C6 motor overloaded Check running amps See specification sheet 1 Fan motor or capacitor 1ph only failed replace 2 Fan thermostat faulty replace 3 Inverter failed replace 8 Short List of Parts Refer to the burner supplement supplied with the heater Refer to Powrmatic Ltd for the details of other parts quoting the seri...

Page 13: ...he column of exhaust gas Tm 288 Te TL 0 2 0 18 Where Te is the exhaust gas temperature in C TL is the external air temperature in C Wm Mean exhaust gas velocity in m s M A Qm Where A is the cross sectional area of the flue in m2 M is the exhaust gas mass flow in kg s which for this heater is______________ Every effort is made to ensure accuracy at time of going to press However as part of our poli...

Page 14: ...uct improvement we reserve the right to alter specifications without prior notice HEATING DIVISION Hort Bridge Ilminster Somerset TA19 9PS Tel 01460 53535 Fax 01460 52341 BSI Registered Firm FM 414 Ind Comm Air Heaters Air Moving Equipment Natural Smoke Heat Ventilators Powered Supply Extract Fans Systems ISO 9001 ...

Reviews: