Where LNVx F units are required to cover a large floor
area, and in buildings with high roof or ceiling heights
Calecon thermal economiser units may be considered to
ensure even heat distribution and minimise stratification.
Care should be taken to avoid impeding the air throw with
racking, partitions, plant or machinery etc. Various outlet
configurations are available as optional extras to modify
the air throw pattern to suit particular site conditions.
For LNVx CCF units, the duct work must comply to current
regulations and be correctly calculated to match the
particular heaters resistance and air flow.
A full and unobstructed return air path to the air heater(s)
must be provided.
If the air heater(s) are installed in a plant room, the return
air intake(s) and the warm air outlet(s) from the heater(s)
must be fully ducted, into and out of the plant room to
avoid interference with the operation of the heater.
The openings in the structure of the plant room/enclosure
through which the ducting passes must be fire stopped.
Care must be taken to ensure that return-air intakes are
kept clear of sources of smells and fumes, and where
there is any possibility of pollution of the air by dust,
shavings etc., precautions must be taken to prevent
contamination.
If necessary, suitable barrier rails should be provided to
prevent any combustible material being placed within
900mm of the outlets.
Model
Air Volume m³/h
Maximum Duct Resistance (Pa)
LNVx15CCF
1500
220
LNVx20CCF
2020
320
LNVx25CCF
2808
220
LNVx40CCF
4250
150
LNVx45CCF
5450
250
LNVx50CCF
5450
250
LNVx60CCF
6600
250
LNVx70CCF
9200
250
LNVx90CCF
10100
180
LNVx120CCF
12800
250
LNVx140CCF
13500
250
LNVxCCF Heater Unit
It is recommended that you have a
minimum of 2000mm from the heater
outlet prior to any restriction
Airflow