13 

Err.13 

Input phase 
loss 

1.The drive panel is abnormal. 
2.The lightning protection plate is 
abnormal 
3.The main control panel is abnormal 
4.The three-phase input power is not 
normal 

1.Replace the drive, the power 
board or contactor 
2.Seek for technical support 
3.Check and eliminate the existing 
problems in the peripheral line 

14 

Err.14 

Output phase 
loss 

1.The lead wires from the inverter to 
the motor is not normal 
2.The inverter's three phase output is 
unbalanced when the motor is running 
3.The drive panel is abnormal. 
4.The module is abnormal 

1.Eliminate peripheral faults 
2.Check the motor's three-phase 
winding is normal or not and 
eliminate faults 
3.Seek for technical support 

15 

Err.15 

Module 
overheating 

1.The air duct is blocked 
2.The fan is damaged 
3.The ambient temperature is too high 
4.The module thermistor is damaged 
5.The inverter module is damaged 

1.Clean up the air duct 
2.Replace the fan 
3.Decrease the ambient temperature 
4.Replace the thermistor 
5.Replace the inverter module 

16 

Err.16 

External 
equipment fault 

Input external fault signal through the 
multi-function terminal DI 

Reset run 

17 

Err.17 

Communication 
fault 

1.The communication cable is not 
normal 
2.The settings for communication 
expansion card F9.07 are incorrect 
3.The settings for communication 
parameters F9 group are incorrect 
4.The host computer is not working 
properly 

1.Check the communication cable 
2.Correctly set the communications 
expansion card type 
3.Correctly set the communication 
parameters 
4.Check the wiring of host computer 

18 

Err.18  Contactor fault 

1.Input phase loss 
2.The drive plate and the contact are 
not normal 

1.Check and eliminate the existing 
problems in the peripheral line 
2.Replace the drive, the power 
board or contactor 

19 

Err.19 

Current 
detection fault 

1.Check Hall device 
2.The drive panel is abnormal. 

1.Replace the drive panel 
2.Replace hall device 

21 

Err.21 

Motor 
parameter auto 
tuning fault 

1.The motor parameters was not set 
according to the nameplate 
2.The identification process of 
parameter is timeout 

1.correctly set motor parameter 
according to the nameplate 
2.check the lead wire from the 
inverter to the motor 

22 

Err.22  Disk code fault 

1.The encoder is damaged 
2.PG card is abnormal 
3.The encoder model does not match 
4.The encoder connection has error 

1.Replace the encoder 
2.Replace the PG card 
3.Correctly set the encoder model 
according to the Actual conditions 
4.Eliminate the line fault 

23 

Err.23 

EEPROM read 
and write fault 

EEPROM chip is damaged 

Replace the main control panel 

26 

Err.26 

Inverter 
hardware fault 

1.Overvoltage 
2.Overcurrent 

1.Eliminate overvoltage fault 
2.Eliminate overcurrent fault 

27 

Err.27 

Short-circuit to 
ground fault 

Motor short to ground 

Replace the cable or motor 

28 

Err.28 

Cumulative 
running time 
arrival fault 

Cumulative running time arrival fault 

Clear history information by using 
initialization function parameters 

29 

Err.29  Custom fault 1 

Input custom fault 1 signal through the 
multi-function terminal DI 

Reset run 

31 

Err.31  Custom fault 2 

Input custom fault 2 signal through the 
multi-function terminal DI 

Reset run 

40 

Err.40 

Total power-on 
time arrival 
fault 

Total power-on time reaches the set 
value 

Clear history information by using 
initialization function parameters 

41 

Err.41 

Load drop 
fault 

The inverter running current is less 
than F8.31 

Confirm whether the load is 
removed or not or the settings for 
parameter(F8.31, F8.32) accord 
with the Actual operating 
conditions 

42 

Err.42 

PID feedback 
loss when 
running fault 

PID feedback is less than the set value 
of E2.11 

Check PID feedback signal or set 
E2.11 to an appropriate value 

51 

Err.51 

Quick current 
limiting fault 

1.Whether the load is too large or the 
motor stall occurs 
2.The type selection of inverter is 
small 

1.Reduce the load and check the 
motor and its mechanical 
conditions 
2.Choose the inverter with large 
power level 

COF 

Switch motor 
when running 
fault 

Change current motor through the 
terminal when the inverter is running 

Switch motor after the inverter 
stops 

Summary of Contents for PI500 011G2

Page 1: ...maintenance care For any problem within the warranty period please fill out the warranty card and fix it to our authorized dealer 2 Instructions on nameplate Model designation POWTRAN Inverter PI 500...

Page 2: ...ops LOCAL REMOTE Command indicator light That is the indicator for keyboard operation terminal operation and remote operation Communication contral ON terminal control working status OFF keyboard cont...

Page 3: ...range 0m to 6500m Running Input signal DI input terminal 6 digital input terminals DI5 for high speed pulse input 0 to 100 kHz square wave AI1 analog input 1 analog input terminals respectively for o...

Page 4: ...make sure that there is no mistake before power can be turned on 7 Parameter list In PI500A series frequency inverters some parameters are manufacturer reserved and their serial numbers are not liste...

Page 5: ...ting 0 Relative to maximum frequency 1 Relative to master frequency source 1 2 Relative to master frequency source 2 0 F0 06 Frequency source auxiliary setting range 0 to 150 100 F0 07 Frequency super...

Page 6: ...ed to switch between two frequency sources 19 UP DOWN setting Terminal keyboard When the frequency reference is the digital frequency this terminal is used to clear the changed frequency value by term...

Page 7: ...ad warning is exceeded For motor overload parameter setting refer to function codes F8 02 F8 04 7 Frequency inverter overload forecasting alarm The output signal ON 10 seconds before the overload prot...

Page 8: ...git SPA Ten thousands digit Relay 2 00000 F2 16 DA1 zero bias coefficient 100 0 to 100 0 0 0 F2 17 DA1 gain 10 00 to 10 00 1 00 F3 group Start stop control parameters group Code Parameter name Setting...

Page 9: ...verter module radiator temperature 0 0 to 100 0 F6 07 Total run time 0h to 65535h F6 08 Total power on time 0h to 65535h F6 09 Total power consumption 0 to 65535kWh F6 10 Product series number Frequen...

Page 10: ...0 to 300 0 Rated motor current 0 0 F7 40 Module temperature arrival 0 to 100 75 F7 41 Cooling fan control 0 Fan running only when running 1 Fan always running 0 F7 42 Timing function selection 0 Inval...

Page 11: ...depth 0 E0 group Pendulum frequency fixed length and counting parameter array Code Parameter name Setting range Factory setting Chan ge E0 00 Swing setting mode 0 Relative to center frequency 1 Relat...

Page 12: ...h 0 0s h E1 49 15 stage ac deceleration time selection Same as E1 19 0 E1 50 Simple PLC run time unit 0 S seconds 1 H hours 0 E1 51 Multi stage command 0 reference manner 0 Function code E1 00 referen...

Page 13: ...e Setting range Factory setting Cha nge y0 00 Parameter initialization 0 Nno operation 1 Restore default parameter values not including motor parameters 2 Clear history 3 Restore default parameter val...

Page 14: ...ppens 2 The control mode is vector and without identification of parameters 3 The deceleration time is too short 4 The voltage is low 5 Suddenly increase the load in the process of deceleration 6 Didn...

Page 15: ...2 Replace hall device 21 Err 21 Motor parameter auto tuning fault 1 The motor parameters was not set according to the nameplate 2 The identification process of parameter is timeout 1 correctly set mot...

Page 16: ...yboard compartment Dimension drawing of keyboard compartment dimension unit mm PI500 pI500A keyboard installation opening dimension drawing Mounting panel Opening size of external mounting panel Openi...

Reviews: