background image

  7 / 16 

terminal 2 

control), the terminal can be used to decelerate the inverter until stop, at 
the time the deceleration time is fixed for deceleration time 4. 

49 

Deceleration DC 
braking 

If the terminal is valid, firstly the inverter decelerates to the initial 
frequency of stop DC braking, and then switches directly to DC braking 
status. 

50  Clear current running time  If the terminal is valid, the inverter's current running time is cleared 

 

F1.10 

Terminal command mode 

0: Two-wire type 1; 
1: Two-wire type 2; 
2: Three-wire type 1; 
3: Three-wire type 2 

 

F1.11  Terminal UP / DOWN change rate  0.001Hz/s to 65.535Hz/s 

1.000Hz/s 

 

F1.12 

Minimum input for AIC1 

0.00V to F1.14 

0.30V 

 

F1.13 

F1.12 corresponding setting 

-100.0% to +100.0% 

0.0% 

 

F1.14 

Maximum input for AIC1 

F1.12 to +10.00V 

10.00V 

 

F1.15 

F1.14 corresponding setting 

-100.0% to +100.0% 

100.0% 

 

F1.25 

AI input setting selection 

Units digit:AI1 Below the minimum input 
setting selection   
0: Corresponding to the minimum input set; 
1:0.0%; 

000 

 

F1.26 

HDI Minimum input 

0.00kHz to F1.28 

0.00kHz 

 

F1.27 

F1.26 Corresponding to the set 

-100.0% to +100.0% 

0.0% 

 

F1.28 

HDI Maximun input 

F1.26 to 100.00kHz 

50.00kHz 

 

F1.29 

F1.28 Corresponding to the set 

-100.0% to +100.0% 

100.0% 

 

F1.30 

DI filter time 

0.000s to 1.000s 

0.010s 

 

F1.31 

AI1 filter time 

0.00s to 10.00s 

0.10s 

 

F1.34 

HDI filter time 

0.00s to 10.00s 

0.00s 

 

F1.35 

DI terminal Mode Selection 1 

Units digit:DI1 :   
0:High level active;          1: Low level active 
Tens digit: DI2(Same as the units digit);   
Hundreds digit:DI3(Same as the units digit) 
Thousands digit:DI4 (Same as the units digit);   
Ten thousands digit:DI5(Same as the units digit) 

00000 

 

F1.36 

DI terminal mode selection 2 

Units digit:DI6 ; 
0:High level active;      1:Low high level active 

00000 

 

F1.37 

DI1 delay time 

0.0s to 3600.0s 

0.0s 

 

F1.38 

DI2 delay time 

0.0s to 3600.0s 

0.0s 

 

F1.39 

DI3 delay time 

0.0s to 3600.0s 

0.0s 

 

F1.40 

Define the input terminal repeat 

0:Unrepeatable;        1:Repeatable 

 

F2 group    Output terminal parameter set 

Code 

Parameter name 

Setting range 

Factory 

setting 

Cha

nge 

F2.02 

Relay 1 output function selection (TA1.TB1.TC1) 

0 to 39 

 

F2.04 

SPA output function selection (Collector open circuit 
output terminals) 

 

The functions of the relay and SPA output terminal are described as follows: 

Set 

value 

Function 

Functional Description 

No output 

Output no action 

Frequency inverter 
operation 

Frequency inverter is operation, there is output frequency,(Can be 0) 
there is output signal 

Fault Output (Fault 
outage) 

When the frequency inverter fails and the fault stops, the output.Is 
ON signal   

Frequency Level 
detection FDT1 output 

Please Refer function code F7.23, F7.24   

Frequency arrival 

Please Refer function code F7.25 

Zero-speed operation (No 
output when shutdown) 

When the frequency inverter runs and the output frequency is 0, the 
output signal is ON. The signal is OFF when the converter is down. 

Motor overload 
forecasting alarm 

Before motor overload protection action, the output is ON signal, 
after the threshold value of overload warning is exceeded. For motor 
overload parameter setting, refer to function codes F8.02-F8.04. 

Frequency inverter 
overload forecasting 
alarm 

The output signal ON 10 seconds before the overload protection 
occurs. 

Set count value to arrival 

When the count value reaches the value set by E0.08, the output   
signal is ON   

Designated count value 
arrives 

When the count value reaches the value set by E0.09, the ON signal 
is output. Counting function reference E0 group function description 

10 

Length arrival 

When the actual length of detection exceeds the length set by E0.05, 
the output signal is ON. 

11 

PLC cycle completed 

When a simple PLC completes a cycle, it outputs a pulse signal with 
a width of 250ms. 

12 

Accumulated runtime 
arrival 

When the accumulative running time of the converter exceeds the set 
time of F7.21, the output signal is.ON 

13 

Frequency limiting 

When the set frequency exceeds the upper or lower limit frequency, 
and the output frequency of the frequency inverter also exceeds the 
upper or lower limit frequency, the output signal is ON   

14 

Torque limiting 

In the speed control mode, when the output torque reaches the limit 
value of the torque, the frequency inverter is in stall protection state 
and transmits ON signal at the same time. 

15 

Operational readiness 

When the power supply of the main circuit and control circuit of the 
frequency inverter is stable, and the frequency inverter does not detect 
any fault information, and the frequency inverter is in the operational 
state, the output signal is ON   

17 

Upper limit frequency 
arrival 

When the operating frequency reaches the upper limit frequency, the 
output signal is ON. 

18 

Lower limit frequency 
arrival (No output when 
down) 

When the operating frequency reaches the lower limit frequency, the 
ON signal is output. The signal is OFF in downtime. 

19 

Under voltage state output 

When the frequency inverter is under-voltage, the output signal is ON. 

20 

Communication settings 

Please refer to the communication protocol. 

23 

Zero speed operation 2 
(Output when down) 

When the output frequency of the inverter is 0, the ON signal is output. 
The signal is ON when the machine is down. 

24 

Accumulated power-on 
time arrives 

When the accumulative power-on time of the frequency inverter 
(F6.08) exceeds the set time of F7.20, the ON signal is transmitted. 

25 

Frequency level 
detection FDT2 output 

Please refer the function code description F7.26, F7.27   

26 

Frequency 1 arrival ouput 

Please refer the function code description F7.28, F7.29 

27 

Frequency 2 arrival output 

Please refer the function code description F7.30, F7.31   

28 

Current 1 arrival output 

Please refer the function code description F7.36, F7.37   

29 

Current 2 arrival output 

Please refer the function code description    F7.38, F7.39 

30 

Timed output 

When the timing function selection (F7.42) is effective, the ON signal 
is output after the frequency converter reaches the set timing time. 

31 

AI1 input overrun 

When the value of analog input AI1 is greater than F7.51 (Upper limit 
of AI1 input protection) or less than F7.50 (Under AI1 input 
protection).The ON signal is output. 

33 

Reverse operation 

Converter in reverse operation, output ON signal 

Summary of Contents for PI500 011G2

Page 1: ...maintenance care For any problem within the warranty period please fill out the warranty card and fix it to our authorized dealer 2 Instructions on nameplate Model designation POWTRAN Inverter PI 500...

Page 2: ...ops LOCAL REMOTE Command indicator light That is the indicator for keyboard operation terminal operation and remote operation Communication contral ON terminal control working status OFF keyboard cont...

Page 3: ...range 0m to 6500m Running Input signal DI input terminal 6 digital input terminals DI5 for high speed pulse input 0 to 100 kHz square wave AI1 analog input 1 analog input terminals respectively for o...

Page 4: ...make sure that there is no mistake before power can be turned on 7 Parameter list In PI500A series frequency inverters some parameters are manufacturer reserved and their serial numbers are not liste...

Page 5: ...ting 0 Relative to maximum frequency 1 Relative to master frequency source 1 2 Relative to master frequency source 2 0 F0 06 Frequency source auxiliary setting range 0 to 150 100 F0 07 Frequency super...

Page 6: ...ed to switch between two frequency sources 19 UP DOWN setting Terminal keyboard When the frequency reference is the digital frequency this terminal is used to clear the changed frequency value by term...

Page 7: ...ad warning is exceeded For motor overload parameter setting refer to function codes F8 02 F8 04 7 Frequency inverter overload forecasting alarm The output signal ON 10 seconds before the overload prot...

Page 8: ...git SPA Ten thousands digit Relay 2 00000 F2 16 DA1 zero bias coefficient 100 0 to 100 0 0 0 F2 17 DA1 gain 10 00 to 10 00 1 00 F3 group Start stop control parameters group Code Parameter name Setting...

Page 9: ...verter module radiator temperature 0 0 to 100 0 F6 07 Total run time 0h to 65535h F6 08 Total power on time 0h to 65535h F6 09 Total power consumption 0 to 65535kWh F6 10 Product series number Frequen...

Page 10: ...0 to 300 0 Rated motor current 0 0 F7 40 Module temperature arrival 0 to 100 75 F7 41 Cooling fan control 0 Fan running only when running 1 Fan always running 0 F7 42 Timing function selection 0 Inval...

Page 11: ...depth 0 E0 group Pendulum frequency fixed length and counting parameter array Code Parameter name Setting range Factory setting Chan ge E0 00 Swing setting mode 0 Relative to center frequency 1 Relat...

Page 12: ...h 0 0s h E1 49 15 stage ac deceleration time selection Same as E1 19 0 E1 50 Simple PLC run time unit 0 S seconds 1 H hours 0 E1 51 Multi stage command 0 reference manner 0 Function code E1 00 referen...

Page 13: ...e Setting range Factory setting Cha nge y0 00 Parameter initialization 0 Nno operation 1 Restore default parameter values not including motor parameters 2 Clear history 3 Restore default parameter val...

Page 14: ...ppens 2 The control mode is vector and without identification of parameters 3 The deceleration time is too short 4 The voltage is low 5 Suddenly increase the load in the process of deceleration 6 Didn...

Page 15: ...2 Replace hall device 21 Err 21 Motor parameter auto tuning fault 1 The motor parameters was not set according to the nameplate 2 The identification process of parameter is timeout 1 correctly set mot...