- 160 -
第
十
章
Ap
p
en
d
ix
V
Appendix V: Instruction of Profitbus –DP
communication card
V-1.Outline
9KDP1 meet the international standard PROFIBUS fieldbus, powtran technology 9K series
inverter use it together to achieve the drive to become a part of fieldbus complete control of real
fieldbus. Before using this product, please carefully read this manual
V-2 Terminal function
V-2-1
DIP switch description
Switch
position
No.
Function
I`nstruction
1,2
DP Card and the
drive baud rate
selection
Bit 1
Bit 2
Baud Rate
OFF
OFF
115.2K
OFF
ON
208.3K
ON
OFF
256K
ON
ON
512K
3-8
Profibus-DP
Communication
from the station
address
6 Binary Consisting of 64-bit binary address, more than 64 outside
the address can be set only by function code. The following lists some
slave address and switch settings
Address switch settings
0 00 0000
7 00 0111
20 01 0100
Table V-1
:
Switch Functions
V-2-2 Terminal Function
1)
External communication terminal J4-6PIN
Terminal
NO
Mark
Function
Terminal
NO
Logo
Function
1
GND 5V power ground
4
TR+ Cable Positive
2
RTS Request to send signal
5
+5V 5Vpower
3
TR-
Cable negative
6
E
The grounding end
Table V-2
:
External communication terminal function
2)
Upper machine communication interface SW1-8PIN
Terminal
No
Terminal
logo
Function
Terminal
No
Terminal
logo
Function
1
BOOT0 ARM boot selection
5
PC232T
PC 232 communication Sending
side
2
GND
Power ground
6
PC232R
PC 232 communication receiving
side
3
VCC
Power
7
RREST ARM reset
4
Reserved Reserve
8
GND
Power ground
Table V-3
:
PC communication terminal function
V-2-3 LED Light function
LEDlight
Function definition
Description
Green
Power light
If DP card and drive interfaces connected, the inverter after
power LED should be in the steady state
Red
DP CARDS and
DP Card and inverter connected to the normal state of the