Chapter 5 Function parameter
66
Ch
ap
ter 5
conversion of the motor rotation direction.
Tip: after the parameter is initialized, the motor running direction will be restored to its
original status. When the system debugging is completed, please use with caution where the
change of motor steering is strictly prohibited.
F0.25 Reserve
F0.26 Reserve
F0.27 Inverter type
G type (constant torque load type)
1
-
●
F type (fans/pumps load type)
2
The parameters is only for user to view the factory model and can not be changed.
1: Suitable for constant torque load 2: Suitable for variable torque load (fans, pumps load)
5-2-3.
Input terminal
:
F1.00-F1.46
PI500 series inverter comes standard with eight multifunctional digital input terminals (where
DI5 can be used as high-speed pulse input terminal), three analog input terminals.
Code Parameter name
Setting range
Factory
setting
Chan
ge
F1.00
DI1 terminal function selection
0~51
1
★
F1.01
DI2 terminal function selection
0~51
2
F1.02
DI3 terminal function selection
0~51
0
F1.03
DI4 terminal function selection
0~51
9
F1.04
DI5 terminal function selection
0~51
12
F1.05
DI6 terminal function selection
0~51
13
F1.06
DI7 terminal function selection
0~51
0
F1.07
DI8 terminal function selection
0~51
0
F1.08
Undefined
F1.09
Undefined
These parameters are used to set the digital multi-function input terminal, the optional
functions are shown in the following table:
Set
value
Function
Description
0
No function
The terminal for not use can be set to "no function" to prevent
accidental operation.
1
Forward run (FWD)
External terminals are used to control the FWD/REV run mode
of inverter.
2
Reverse run (REV)
3
Three-wire operation
control
This terminal is used to determine the inverter's three-wire
control mode. For details, please refer to the instructions of
function code F1.10 ("terminal command mode).
4
Forward JOG(FJOG) FJOG means Forward JOG running, RJOG means Reverse JOG
running. For Jog running frequency and Jog Ac/deceleration
time, please refer to the description of the function code F7.00,
F7.01, F7.02.
5
Reverse JOG(RJOG)
6
Terminal UP
Modify frequency increment/decrement command when the
frequency is referenced by external terminal. Adjust up/down the
set frequency when the digital setting is selected as the
frequency source.
7
Terminal DOWN
8
Free stop
The inverter output is blocked, at the time, the parking process
of motor is not controlled by the inverter. This way is same as
the principle of free stop described in F3.07.
9
Fault reset (RESET)
The function make use of terminal for fault reset. It has same
function with RESET key on the keyboard. This function can be
used to realize remote fault reset.