MAINTENANCE

 

In the table below, some PROBLEMS will be mentioned — DEFECTS, PROBABLE 

CAUSES AND CORRECTIONS — that may occur in your Operator. Before any 

maintenance, it is necessary to completely disconnect the electrical network.

DEFECTS

PROBABLE CAUSES

CORRECTIONS

Motor does not 

start / does not 

move

A) Power off

B) Open / blown fuse

C) Locked gate

D) Defective limit switch

A) Make sure the electrical network 

is connected correctly

B) Replace fuse with same 

specification

C) Make sure there is no object 

blocking the gate operation

D) Replace the course end system 

(analog and/or digital)

Engine blocked

A) Inverted motor connection

B) Locked gate or trigger

A) Check motor wires

B) Put in manual mode and check 

separately

Electronics board 

does not accept 

command

A) Blown fuse

B) Mains disconnected (power)

C) Defect in remote control 

unloaded

D) Transmitter range (remote 

control)

A) Replace the fuse

B) Connect the network (power)

C) Check and replace battery

D) Check the position of the 

receiver antenna and, if necessary, 

reposition it to ensure reach

Motor only rotates 

to one side

A) Inverted motor wires

B) Inverted limit switch system

C) Defect in command board

A) Check motor connection

B) Invert the connector at the limit 

switch (analog and/or digital)

C) Replace the command board

When connecting and using the outlet for operating external devices, the 

recommended is to use wire with a gauge of 2.5 mm² 110V or 220V. 

Summary of Contents for DZ BRUTALLE 2.0T JetFlex

Page 1: ...ction manual DZ BRUTALLE Technical Manual P30452 04 2022 Rev 1 Made by Motoppar Ind stria e Com rcio de Automatizadores Ltda Av Dr Labieno da Costa Machado 3526 Distrito Industrial Gar a SP CEP 17406...

Page 2: ...ICAL CHARACTERISTICS 5 TOOLS REQUIRED FOR INSTALLATION 6 ELECTRICAL INSTALLATION 6 CARE WITH THE ELECTRICAL INSTALLATION 7 GATE CARE BEFORE AUTOMATION 8 INSTALLATION AND FIXING OF THE OPERATOR 9 ANALO...

Page 3: ...mandatory when installing the operator TECHNICAL CHARACTERISTICS DZ BRUTALLE 3 0T Z12 Z17 TYPE OF OPERATOR Sliding MODEL JetFlex RATED VOLTAGE 127V 220V NOMINAL FREQUENCY 60 Hz RATED POWER 180W 150W E...

Page 4: ...be a flexible cable 3 x 0 75 mm 500 V according to the NBR standard NM 247 5 The power conductor of a product for external use must be a flexible cable 3 x 0 75 mm 500 V as per the standard IEC 60245...

Page 5: ...that uses a straight section Picture A angle presents greater friction and consequently greater wear The circular section Picture B allows for better gate displacement and less friction for the opera...

Page 6: ...ng the set against the gate Then mark the fixing holes in the floor or concrete base 5th Step Drill holes for fixing positioning the operator aligned with the gate Before tightening the 1 2 x 4 parabo...

Page 7: ...rew every 300 or 400 mm 8th Step If the gate leaf is warped provide wedges to ensure rack alignment There are cases where the rack will need to extend the length of the sheet In this case provide a Fr...

Page 8: ...the operator s REED This magnet will act as the opening limit switch 3rd Step Start the engine and observe if the REED s are shutting down correctly If necessary invert the board connector Once the m...

Page 9: ...ace fuse with same specification C Make sure there is no object blocking the gate operation D Replace the course end system analog and or digital Engine blocked A Inverted motor connection B Locked ga...