BASIC TOOLS NEEDED FOR INSTALLATION
Tools needed:
ELECTRICAL CONNECTIONS
For the electrical set-up, the power grid must have the following features:
- 127 V / 220 V Power Supply;
- 5A Circuit Breakers in the Electrical Panel;
- 3/4” diameter conduits between the electrical panel and the disconnection de-
vice;
- 3/4” diameter conduits between the disconnection device and the outlet;
- 1/2” diameter conduits for optional and external pushbuttons;
- 1/2” diameter conduits for (optional) photocells.
- The cable used for the wiring must comply with the NBR NM
247-3 standards (Brazil);
- The mains cable (of an internal use product) must be a 3 x (Tri
-rated) 0.75 mm² / 500 V flexible cable, according to the NBR NM
247-5 standards (Brazil);
- The mains cable (of an internal use product) must be a 3 x
(Tri-rated) 0.75 mm² / 500 V flexible cable; according to the IEC
60245-57 standards (Brazil).
LINEMAN’S PLIERS
HACKSAW
HEX NUT DRIVER
SCREWDRIVER
OPEN-END
WRENCH
STEPLADDER
WELDING MACHINE
HAMMER
SPIRIT LEVEL
TAPE MEASURE
TRY SQUARE
ELECTRIC DRILL
PENCIL
ELECTRIC SANDER /
HAND GRINDER
WIRING PRECAUTIONS
In order to avoid damage to the wiring, it is important that all electrical conductors
are properly connected to the operator. The passing of the cables must be carried
out through conduits, inside the foundation, ensuring that none of the electrical
conductors are stuck and damaged.
The ground terminal must be
connected to the ground wire.
IMPORTANT
The operator must be powered through a Differential Residual (DR)
Current device with a Nominal residual operating current not exce-
eding 30 mA.
DISCONNECTION
DEVICE
CONDUIT