BASIC TOOLS NEEDED FOR INSTALLATION

Tools needed:

ELECTRICAL CONNECTIONS

 For the electrical set-up, the power grid must have the following features:

- 127 V / 220 V Power Supply;

- 5A Circuit Breakers in the Electrical Panel;

- 3/4” diameter conduits between the electrical panel and the disconnection de-

vice;

- 3/4” diameter conduits between the disconnection device and the outlet;

- 1/2” diameter conduits for optional and external pushbuttons;

- 1/2” diameter conduits for (optional) photocells.

- The cable used for the wiring must comply with the NBR NM 

247-3 standards (Brazil);

- The mains cable (of an internal use product) must be a 3 x (Tri

-rated) 0.75 mm² / 500 V flexible cable, according to the NBR NM 

247-5 standards (Brazil);

- The mains cable (of an internal use product) must be a 3 x 

(Tri-rated) 0.75 mm² / 500 V flexible cable; according to the IEC 

60245-57 standards (Brazil).

LINEMAN’S PLIERS

HACKSAW

HEX NUT DRIVER

SCREWDRIVER

OPEN-END 

WRENCH

STEPLADDER

WELDING MACHINE

HAMMER

SPIRIT LEVEL

TAPE MEASURE

TRY SQUARE

ELECTRIC DRILL

PENCIL

ELECTRIC SANDER /

HAND GRINDER

WIRING PRECAUTIONS

In order to avoid damage to the wiring, it is important that all electrical conductors 

are properly connected to the operator. The passing of the cables must be carried 

out through conduits, inside the foundation, ensuring that none of the electrical 

conductors are stuck and damaged.

The ground terminal must be 

connected to the ground wire.

IMPORTANT

The operator must be powered through a Differential Residual (DR) 

Current device with a Nominal residual operating current not exce-

eding 30 mA.

DISCONNECTION

DEVICE

CONDUIT

Summary of Contents for DZ HUB

Page 1: ...TIC GATE OPERATORS LTD 3526 Dr Labieno da Costa Machado Avenue Industrial District Zip Code 17400 000 Gar a SP Brazil www ppa com br 0800 550 250 WARNING Do not use the device with out referring to th...

Page 2: ...CAL FEATURES 5 BASIC TOOLS NEEDED FOR INSTALLATION 6 ELECTRICAL CONNECTIONS 6 WIRING PRECAUTIONS 7 PRECAUTIONS WITH THE GATE BEFORE THE INSTALLATION 8 INSTALLING AND MOUNTING THE OPERATOR 9 INSTALLING...

Page 3: ...g the operator make sure the gate system is placed far enough from the sidewalk The system s power supply network MUST include a disconnection device not su pplied TECHNICAL FEATURES TYPE OF GATE OPER...

Page 4: ...andards Brazil The mains cable of an internal use product must be a 3 x Tri rated 0 75 mm 500 V flexible cable according to the IEC 60245 57 standards Brazil LINEMAN S PLIERS HACKSAW HEX NUT DRIVER SC...

Page 5: ...the system that uses a V track Picture A Corner bead there are many point of friction and therefore increased wear and tear whereas the system that uses a round bar gate track Pic ture B allows the g...

Page 6: ...perator with the gate by placing the toothed rack on the pinion and leaning this set to the gate Then mark the position of the fastening holes on the ground or concrete foundation Step 5 Drill the fas...

Page 7: ...tightening screws every 300 or 400 mm 11 82 or 15 75 in Step 8 If the gate leaf is warped provide holders to ensure the rack bar is aligned In cases where the rack bar is longer than the length of the...

Page 8: ...or and check if the reeds are correctly turning off If necessary reverse the connector of the control board After mounting the magnet holder assemblies perform the final adjustments mo ving them left...

Page 9: ...r cable is correctly inserted in the power outlet B Substitute the fuse for another one with the same specifications C Ensure there are no obstruction on the gate travel D Substitute the analog and or...

Reviews: