12
Parameter Description
Settings
(Default Value)
PV UNITS
Select Temperature units in °C or °F for Thermocouple or Pt100
sensor.
For DC Linear input (mA/mV/V), Select appropriate Units from the
list in Table 5.3. Note however that the selected Units are for the
purpose of indication on Lower Readout only.
-1999.9 to 3000.0
(Default : 100.0)
DC RANGE LOW
(Applicable only for DC Linear Inputs)
The process value corresponding to the Signal Low value from the
transmitter. For more Description Refer Appendix-A.
-1999.9 to 3000.0
(Default : 0.0)
Refer Table 5.3
(Default : ºC)
User Manual
SCANEX PLUS
(Default : Disable)
Enable
Disable
BOTTOM CLIPPING ENABLE
(Applicable only for DC Linear Inputs)
Refer Appendix-B.
-1999.9 to Top Clipping
Default: 0.0
BOTTOM CLIPPING
(Applicable only for DC Linear Inputs)
Refer Appendix-B.
SIGNAL HIGH
(Applicable only for DC Linear Inputs)
The transmitter output signal value corresponding to Range High
process value. For more Description Refer Appendix-A.
SIGNAL LOW
(Applicable only for DC Linear Inputs)
The transmitter output signal value corresponding to Range Low
process value. For more Description Refer Appendix-A.
Input Type
Settings
Default
0 to 20 mA
0.00 to Signal High
0.00
4 to 20 mA
0 to 80 mV
0 to 1.25 V
0 to 5 V
0 to 10 V
1 to 5 V
4.00 to Signal High
0.00 to Signal High
0.000 to Signal High
0.000 to Signal High
0.00 to Signal High
1.000 to Signal High
4.00
0.00
0.000
0.000
0.00
1.000
Input Type
Settings
Default
0 to 20 mA
4 to 20 mA
0 to 80 mV
0 to 1.25 V
0 to 5 V
0 to 10 V
1 to 5 V
Signal Low to 20.00
20.00
20.00
80.00
1.250
5.000
10.00
5.000
Signal Low to 20.00
Signal Low to 80.00
Signal Low to 1.250
Signal Low to 5.000
Signal Low to 10.00
Signal Low to 5.000
DC RANGE HIGH
(Applicable only for DC Linear Inputs)
The process value corresponding to the Signal High value from
the transmitter. For more Description Refer Appendix-A.