3
User Manual
SCANEX PLUS
Figure 1.8
Line
Neutral
2 Pole
Isolating Switch
Fuse
Power Supply Terminals
69
70
L
N
As standard, the module is supplied with power connections suited for 85 to 264 VAC line supply. Use well-insulated copper
conductor wire of the size not smaller than 0.5mm² for power supply connections ensuring proper polarity as shown in Figure
1.8. The module is not provided with fuse and power switch. If necessary, mount them separately. Use a time lag fuse rated 1A
@ 240 VAC.
POWER SUPPLY
RELAY OUTPUTS
There are 4 Relay Outputs provided for common alarms. The relay connections are shown in Figure 1.7 below.
Figure 1.7
Potential-free Relay changeover contacts NO (Normally
Open) and C (Common) rated 10A/240VAC (resistive
load) are provided as Relay output.
AC
LOAD
Relay Output Terminals
NO
C
DC