ELECTRICAL SpECIFICATIONS:
Specifications range:
-20°C to +60°C
Common specifications:
Isolation, test / operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 .75 kVAC / 250 VAC
Power derating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . T
amb .
> 25°C, 0 .4 VA/°C
EMC immunity influence . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < ±0 .5% of span
Relative air humidity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . < 95% RH (non-cond .)
Dimensions (HxWxD) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 .5 x 35 .5 x 84 .5 mm
Protection degree . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IP50
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 600 g
Input:
Primary voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207 . . .253 VAC
97 .75 . . .132 .25 VAC
Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50 . . .60 Hz
Output:
Secondary voltage (loaded) . . . . . . . . . . . . . . . . . . . . . . . . 24 VAC / 1 .25 A
Secondary voltage (unloaded) . . . . . . . . . . . . . . . . . . . . 28 VAC
Secondary voltage (loaded) . . . . . . . . . . . . . . . . . . . . . . . . 12 VAC / 2 .50 A
Secondary voltage (unloaded) . . . . . . . . . . . . . . . . . . . . 14 VAC
GOST R approval:
VNIIM
Observed authority requirements:
Standard:
EMC 2004/108/EC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . EN 61326-1
LVD 2006/95/EC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . EN 61010-1
PELV/SELV . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . IEC 364-4-41 and EN 60742
Of span = Of the presently selected range
TRANSFORMER 2240
• Double-isolated transformer
• 3 .75 kVAC isolation voltage
• 30 VA ring core transformer
• Thermal overload protection
• 12 or 24 VAC secondary voltage
• Standard 11-pole relay socket
AppLICATIONS:
Transformer for supply of components with 12 or 24 VAC supply voltage .
Transformer for stabilised DC power supplies, e .g . type 2229 .
TECHNICAL CHARACTERISTICS:
Ring core transformer with separate 3 .75 kVAC isolation voltage between primary
and secondary windings . The transformer is fitted with a thermal 100°C fuse .
Two transformers may be paralleled for higher output power . The transformer is
molded into the cassette and should be mounted with 10 mm distance to the
adjacent cassette for optimal cooling .
The load diagram shows the relation between the ambient temperature and
maximum VA output . The module is supplied with a retention clip for a safe
attachment to the relay socket .
MOuNTING:
The 2240 is for standard 11-pole socket mounting in all positions . To achieve
maximum cooling of the module, mounting in a vertical position at a distance of
10 mm between neighbouring units is recommended .
INpuT:
Standard primary voltages of 115 or 230 VAC . Special primary voltages may be
delivered, but are not kept in stock .
OuTpuT:
Standard secondary voltages of 12 or 24 VAC . Max DC power after rectifica tion
and stabilisation: 20 W . Special secondary voltages may be delivered, but are
not kept in stock .