9106QI01
LERBAKKEN 10, 8410 RØNDE DENMARK
Revision date:
2020-06-18
Version Revision
V6 R0
Prepared by:
PB
Page:
1/6
IECEx Installation drawing
For safe installation of 9106B the following must be observed. The module shall only be
installed by qualified personnel who are familiar with the national and international laws,
directives and standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
For Installation in Zone 2 the following must be observed.
The 4501 programming module is to be used solely with PR electronics modules. It is important
that the module is undamaged and has not been altered or modified in any way. Only 4501
modules free of dust and moisture shall be installed.
9106B1A: 1 channel �ART� -transparent repeater (27.5V Barrier)
9106B1B: 2 channel �ART� -transparent repeater (27.5V Barrier)
9106B2A: 1 channel �ART� -transparent repeater (25.3V Barrier)
9106B2B: 2 channel �ART� -transparent repeater (25.3V Barrier)
IECEx Certificate
: ……………… IECEx DEK 11.0084X
Marking 9106Bxx
[Ex ia Ga] IIC/IIB/IIA
[Ex ia Da] IIIC
[Ex ia Ma] I
Marking 9106Bxx, 9106Axx
Ex ec nC IIC T4 Gc
Standards
IEC60079-11:2011, IEC60079-0: 2017, IEC60079-15 :2017,
IEC60079-7:2015+A1:2017
Supply terminal
(31,32)
Voltage:
19.2 – 31.2VDC
Status Relay
. terminal (33,34) Zone 2 installation
Voltage max:
125 VAC / 110 VDC 32 VAC / 32 VDC
Power max:
62.5 VA / 32 W 16 VA / 32 W
Current max:
0.5 A AC / 0.3 ADC 0.5 A AC / 1 ADC
Installation notes:
Install in pollution degree 2, overvoltage category II as defined in IEC 60664-1
Do not separate connectors when energized and an explosive gas mixture is present.
Do not mount or remove modules from the Power Rail when an explosive gas mixture is present.
Disconnect power before servicing.
The wiring of unused terminals is not allowed.
The Loop Supply and Current Input terminals for the same channel shall not be applied at the
same time.
In type of protection [Ex ia Da] the parameters for intrinsic safety for gas group IIB are applicable.
For installation in Zone 2, the module shall be installed in an enclosure in type of protection Ex n or
Ex e, providing a degree of protection of at least IP54. Cable entry devices and blanking elements
shall fulfill the same requirements.
For installation on Power Rail in Zone 2, only Power Rail type 9400 supplied by Power Control Unit
type 9410 (Type Examination Certificate KEMA 07ATEX0152 X) is allowed.
IECEx Installation Drawing
9106 - Product version 9106-002
21