32
9106 - Product version 9106-002
9106QA01
LERBAKKEN 10, 8410 RØNDE DENMARK
Revision date:
2020-06-18
Version Revision
V6 R0
Prepared by:
PB
Page:
6/6
9106Axx, 9106Bxx, Installation:
Hazardous area
Zone 2
Supply:
19.2 – 31.2 VDC
(terminal 31,32)
(terminal 91,92,93,94,95)
Input
CH1 (terminal 43,44)
CH2 (terminal 53,54)
Status Relay. terminal (33,34)
Zone 2 Installation
Voltage max:
125 VAC / 110 VDC
32 VAC / 32 VDC
Power max:
62.5 VA / 32 W
16 VA / 32 W
Current max:
0.5 A AC / 0.3 ADC
0.5 A AC / 1 ADC
For installation in Zone 2, the module shall be installed in an enclosure in type of protection Ex n or
Ex e, providing a degree of protection of at least IP54. Cable entry devices and blanking elements
shall fulfill the same requirements.
For installation on Power Rail in Zone 2, only Power Rail type 9400 supplied by Power Control Unit
type 9410 (Type Examination Certificate KEMA 07ATEX0152 X) is allowed.
For Installation in Zone 2 the following must be observed. The 4501 programming module is to be
used solely with PR electronics modules. It is important that the module is undamaged and has not
been altered or modified in any way. Only 4501 modules free of dust and moisture shall be
installed.
-20 ≤ Ta ≤ 60ºC
Output:
(terminal 11,12,13,14)
44
43
42
41
54
53
52
51
34
33
32
31
14
13
12
11
9106
4501
91 92 93 94 95
Power
Rail
CH1
CH2
T
T
_
+
+
_