9106QF01
LERBAKKEN 10, 8410 RØNDE DENMARK
Revision date:
2019-04-04
Version Revision
V5 R0
Prepared by:
PB
Page:
5/5
(terminal 11,12,13,14)
(terminal 31,32,33,34)
(terminal 91,92,93,94,95)
U
m
: 253V, max 400Hz
9106B1A, 9106B1B, 9106B2A, 9106B2B
Ex input : External current source 1 to 2
CH1 (terminal 42)
CH2 (terminal 51)
U
o
:
0 V
I
o
:
0 mA
P
o
:
0 W
U
i
:
30 V
I
i
:
120 mA
Pi:
0.85 W
C
i
:
4 nF
L
i.
0 μH
-20 ≤Ta ≤ +60ºC
44
43
42
41
54
53
52
51
34
33
32
31
14
13
12
11
9106
4501
91 92 93 94 95
Power
Rail
CH1
CH2
+
-
Simple Apparatus or
Intrinsic safe apparatus
with entity parameters:
Vmax (Ui) ≥ Vt (Uo)
Imax (Ii) ≥ It (Io)
Pi ≥ Pt (Po)
Ca ≥ C
cable
+ Ci
La ≥ L
cable
+ Li
Hazardous Classified Location Unclassified Location or
Class I/II/III, Division 1, Group A,B,C,D,E,F,G
Hazardous Classified Location
or Class I, Zone 0/1 Group IIC, [AEx ia] IIC Class I, Division 2, Group A,B,C,D T4
or Group IIC, [Ex ia Ga] IIC Gc
or Class I Zone 2 Group IIC T4 Gc
9106 - Product version 9106-002
37