9106QI01
LERBAKKEN 10, 8410 RØNDE DENMARK
Revision date:
2016-11-30
Version Revision
V5 R0
Prepared by:
PB
Page:
2/5
Hazardous area Non Hazardous area
Zone 0,1,2, 20, 21, 22
or Zone 2
9106B1A, 9106B1B
Ex input: Loop current source
CH1 (terminal 43,44)
CH2 (terminal 53,54)
U
o
:
27.5 V
I
o
:
92.6 mA
P
o
:
0.64 W
IIC
IIB
IIA
I
C
o.
0.084
F 0.670
F
2.23
F
3.94
F
L
o.
4.15 mH 16.59 mH
33.17 mH
54.42 mH
L
o/
R
o
--------
223 µH/Ω 447 µH/Ω
733 µH/Ω
-20 ≤Ta ≤ +60ºC
(terminal 11,12,13,14)
(terminal 31,32,33,34)
(terminal 91,92,93,94,95)
U
m
: 253 V, max. 400 Hz
44
43
42
41
54
53
52
51
34
33
32
31
14
13
12
11
9106
4501
91 92 93 94 95
Power
Rail
CH1
CH2
T
T
_
+
+
_
9106B2A, 9106B2B
Ex input: Loop current source
CH1 (terminal 43,44)
CH2 (terminal 53,54)
U
o
:
25.3 V
I
o
:
96 mA
P
o
:
0.61 W
IIC
IIB
IIA
I
C
o.
0.104
F 0.818
F 2.85
F
4.74 µF
L
o.
3.86 mH
15.43 mH 30.86 mH
50.64 mH
L
o
/ R
o
---------
234 µH/Ω 468 µH/Ω
769 µH/Ω
22