8
5114V107-UK
CONFIGURATION
The transmitter is configured to the present task by way of a PC and PR
electronics A/S’ communications interface Loop Link. The communications interface
is galvanically isolated to protect the PC port. Communication is 2-way to allow the
retrieval of the transmitter set-up into the PC and to allow the transmission of the
PC set-up to the transmitter. For users who do not wish to do the set-up them-
selves, the 5114 can be delivered configured according to customer specifica tions:
input type, measurement range, sensor error detection, and output signal.
ELECTRICAL SPECIFICATIONS
Specifications range:
-20°C to +60°C
Common specifications:
Supply voltage, universal ..................................... 21.6...253 VAC
50...60 Hz
19.2...300 VDC
Max. required power, 1 / 2 channels ............... 2.1 W / 2.8 W
Fuse ............................................................................... 400 mA SB / 250 VAC
Isolation voltage, test / operation .................... 3.75 kVAC / 250 VAC
PELV/SELV .................................................................. IEC 61140
Communications interface ................................... Loop Link
Signal / noise ratio .................................................. Min. 60 dB (0...100 kHz)
Updating time:
Temperature input ............................................. 115 ms
mA / V / mV input .............................................. 75 ms
Response time (0...90%, 100...10%), programmable:
Temperature input ............................................. 400 ms...60 s
mA / V / mV input .............................................. 250 ms...60 s
Signal dynamics, input ........................................... 22 bit
Signal dynamics, output ....................................... 16 bit
Calibration temperature ........................................ 20...28°C