13
2.6 - Transducer Block Examples Setup
2.6.1 Measurement of RTD with one sensor:
PRIMARY_VALUE_UNIT . . . . . . . = K, °C, °F or °R
LIN_TYPE. . . . . . . . . . . . . . . . . . . . = Any RTD
LIN_TYPE_2 . . . . . . . . . . . . . . . . . = N/A (ignored in setup check)
SENSOR_MEAS_TYPE. . . . . . . . . = PV = SV_1, SV_2 not available
SENSOR_CONNECTION . . . . . . . = 2-, 3- or 4-wire
SENSOR_CONNECTION_2 . . . . . = N/A (ignored in setup check)
RJ_TYPE . . . . . . . . . . . . . . . . . . . . . = N/A (ignored in setup check)
Connections:
2.6.2 Measurement of RTD with two sensors:
PRIMARY_VALUE_UNIT . . . . . . . = K, °C, °F or °R
LIN_TYPE. . . . . . . . . . . . . . . . . . . . = Any RTD
LIN_TYPE_2 . . . . . . . . . . . . . . . . . = Any RTD
SENSOR_MEAS_TYPE. . . . . . . . . = Anything, but not "PV = SV_1, SV_2 not available"
SENSOR_CONNECTION . . . . . . . = 2- or 3-wire
SENSOR_CONNECTION_2 . . . . . = Default set to 2-wire
RJ_TYPE . . . . . . . . . . . . . . . . . . . . . = N/A (ignored in setup check)
Connections:
2.6.3 Measurement of thermocouple with one sensor:
PRIMARY_VALUE_UNIT . . . . . . . = K, °C, °F or °R
LIN_TYPE. . . . . . . . . . . . . . . . . . . . = Any TC
LIN_TYPE_2 . . . . . . . . . . . . . . . . . = N/A (ignored in setup check)
SENSOR_MEAS_TYPE. . . . . . . . . = PV = SV_1, SV_2 not available
SENSOR_CONNECTION . . . . . . . = N/A (ignored in setup check)
SENSOR_CONNECTION_2 . . . . . = N/A (ignored in setup check)
RJ_TYPE . . . . . . . . . . . . . . . . . . . . . = No Reference Junction, Internal, External (constant value),
Sensor 2-wire or Sensor 3-wire
Connections:
Connections with two sensors
can be configured for
2 measurements, difference,
average or redundancy