35
LO_PRI
52
Priority of the low alarm.
Un-
signed
8
SRC
1
R/W
0
15
0
LO_LIM
53
The setting for the low alarm in engineering units.
Float
SRC
4
R/W -INF
PV_
SCALE
-INF
LO_LO_PRI
54
Priority of the low low alarm.
Un-
signed
8
SRC
1
R/W
0
15
0
LO_LO_LIM
55
The setting of the low low alarm in engineering units.
Float
SRC
4
R/W -INF
PV_
SCALE
-INF
DV_HI_PRI
56
Priority of the high deviation alarm.
Un-
signed
8
SRC
1
R/W
0
15
0
DV_HI_LIM
57
The setting of the high deviation alarm limit in engineering
units.
Float
SRC
4
R/W
0
PV
span
+INF
DV_LO_PRI
58
Priority of the low deviation alarm.
Un-
signed
8
SRC
1
R/W
0
15
0
DV_LO_LIM
59
The setting of the low deviation alarm limit in engineering
units.
Float
SRC
4
R/W -PV
span
0
-INF
HI_HI_ALM
60
The status for high high alarm and its associated time stamp. DS-71
D
16
R/W
HI_ALM
61
The status for high alarm and its associated time stamp.
DS-71
D
16
R/W
LO_ALM
62
The status of the low alarm and its associated time stamp.
DS-71
D
16
R/W
LO_LO_ALM
63
The status of the low low alarm and its associated time
stamp.
DS-71
D
16
R/W
DV_HI_ALM
64
The status and time stamp associated with the high devia-
tion alarm.
DS-71
D
16
R/W
DV_LO_ALM
65
The status and time stamp associated with the low deviation
alarm.
DS-71
D
16
R/W