16
9106 - Product Version 9106-001
CONFIGURATION /
OPERATING THE FUNCTION KEYS
Documentation for routing diagram.
In general
When configuring the 9106, you will be guided through all parameters and you
can choose the settings which fit the application. For each menu there is a
scrolling help text which is automatically shown in line 3 on the display.
Configuration is carried out by use of the 3 function keys:
1
will increase the numerical value or choose the next parameter
2
will decrease the numerical value or choose the previous parameter
3
will save the chosen value and proceed to the next menu
When configuration is completed, the display will return to the default state
1.0. Pressing and holding
3
will return to the previous menu or return to the
default state (1.0) without saving the changed values or parameters.
If no key is activated for 1 minute, the display will return to the default state
(1.0) without saving the changed values or parameters.
Further explanations
Password protection:
Programming access can be blocked by assigning a
password. The password is saved in the device in order to ensure a high
degree of protection against unauthorised modifications to the configuration.
Default password 2008 allows access to all configuration menus.
Loop limits
In the menus LO.LIM and HI.LIM you can choose the current values which will
trigger a loop error alarm from the status relay. The NAMUR NE43 limits are
selected by setting LO.LIM at 3.6 mA and HI.LIM at 21 mA. The selected
limits are identical for both channels. This function can be deactivated by
selecting limits outside the range 3.5...23 mA. Alternatively, the status relay
can be used as a simple limit switch in the 1-channel version.
The loop break limit is fixed <= 1 mA. If this limit is exceeded, the status relay
will be de-energized.