IECEx Installation drawing
9116
For safe installation of 9116B the following must be observed. The module shall only be installed by
qualified personnel who are familiar with the national and international laws, directives and
standards that apply to this area.
Year of manufacture can be taken from the first two digits in the serial number.
4501
For Installation in Zone 2 the following must be observed.
The 4501 programming module is to be used solely with PR electronics modules. It is important
that the module is undamaged and has not been altered or modified in any way. Only 4501
modules free of dust and moisture shall be installed.
IECEx Certificate: ...................................................................... .KEM 10.0022X
Marking: .....................................................................................
Standards
IEC60079-15:2005, IEC60079-11:2011, IEC60079-0:2011
IEC60079-26:2006
-20
≤
Ta
≤
+60ºC
(terminal 11,12,13,14)
(terminal 31,32,33,34)
(terminal 91,92,93,94,95)
U
m
: 253 V; max. 400 Hz
Hazardous area
Zone 0, 1, 2, 20, 21 and 22
Non Hazardous area
or Zone 2
Status relay, terminal (33,34)
Non hazardous area installation
Voltage max: 125 VAC / 110 VDC
Power max:
62.5 VA / 32 W
Current max: 0.5 A AC / 0.3 ADC
Zone 2 installation:
Voltage max: 32 VAC / 32 VDC
Power max:
16 VA / 32 W
Current max: 0.5 A AC / 1 A DC
Relay output, terminal (13,14)
Non hazardous area installation
Voltage max: 250 VAC / 30 VDC
Power max:
500 VA / 60 W
Current max: 2 A AC / 2 ADC
Zone 2 installation
Voltage max: 32 VAC / 30 VDC
Power max:
64 VA / 60 W
Current max: 2 A AC / 2 ADC
4- wire
2- wire
3- wire
-
TC
RTD / LinR
+
Potm. 2
Potm. 3
Potm. 1
+
mA
Loop
V
+
T
54
53
52
51
44
43
42
41
9116
34
33
32
31
14
13
12
11
Power Rail
4501
+
+
-
-
-
[Ex ia Ga] IIC/IIB/IIA
Ex nA nC IIC T4 Gc
[Ex ia Da] IIIC
[Ex ia Ma] I