9116 - Product Version 9116-003
35
9116QI01
LERBAKKEN 10, 8410 ROENDE DENMARK
Revision date:
2012-07-04
Version Revision
V6 R0
Prepared by:
PB
Page:
4/4
Uo
16.6 V
IIC
0.4
μ
F
100 mH 25mH/
Ω
Io
0.2 mA
IIB
2.3
μ
F
100 mH 100mH/
Ω
Po
0.8 mW
IIA
9.5
μ
F
100 mH 200mH/
Ω
Lo/Ro
Module 9116B 1/2
Term. 52-51, 51-52
Group
Co
Lo
Terminal 51-52
Ui
30 V
Ii
120 mA
Pi
900 mW
Ci
3 nF
Li
2
μ
H
Module 9116B 1/2
Hazardous area
Non Hazardous area
Zone 0, 1, 2, 20, 21, 22
or Zone 2
+
-
54
53
52
51
44
43
42
41
9116
34
33
32
31
14
13
12
11
Power Rail
4501
54
53
52
51
44
43
42
41
9116
34
33
32
31
14
13
12
11
Power Rail
4501
(terminal 11,12,13,14)
(terminal 31,32,33,34)
(terminal 91,92,93,94,95)
U
m:
253 V max. 400 Hz
-20
≤
Ta
≤
+60ºC
0/4-20 mA
Current source
Status relay, terminal (33,34)
Non hazardous area installation
Voltage max: 125 VAC / 110 VDC
Power max:
62.5 VA / 32 W
Current max: 0.5 A AC / 0.3 ADC
Zone 2 installation:
Voltage max: 32 VAC/ 32 VDC
Power max:
16 VA / 32 W
Current max: 0.5 A AC / 1 A DC
Relay output, terminal (13,14)
Non hazardous area installation
Voltage max: 250VAC / 30VDC
Power max:
500VA / 60W
Current max: 2A AC / 2ADC
Zone 2 installation
Voltage max: 32 VAC / 30 VDC
Power max:
64 VA / 60 W
Current max: 2 A AC / 2 ADC