Current input, Current output
Probability of dangerous Failure per Hour (PFH)
4.20E-08
Note
1
Probability of failure on demand (PFD) -
1 year proof test interval
2.77E-04
Proof test interval (10% of loop PFD)
5 years
Safe Failure Fraction
95%
Current input, Relay output
Probability of dangerous Failure per Hour (PFH)
6.20E-08
Note
1
Probability of failure on demand (PFD) -
1 year proof test interval
4.00E-04
Proof test interval (10% of loop PFD)
3 years
Safe Failure Fraction
93%
Common Safety Parameters
Demand response time
Signal input: < 0.5 seconds
Potentiometer and linear resistance
input < 0.65 seconds
Temperature input: < 1.1 seconds
Demand mode
High
Demand rate
3000 seconds
Mean Time To Repair (MTTR)
24 hours
Diagnostic test interval
30 seconds
Hardware Fault Tolerance (HFT)
0
Component Type
B
SIL capability
SIL 2
Description of the “Safe State”, analogue output
Output
≤
3.6 mA or
Output
≥
21 mA
Description of the “Safe State”, relay output
Contact open (relay de-energized)
Relay lifetime (Note2)
100 000 times
Note1: The 9116 contains no lifetime limiting components, therefore the PFH figures are valid
for up to 12 years, according to IEC 61508.
Note2: The user must calculate the product lifetime with regard to the relay lifetime.
8 Hardware and software configuration
All configurations of software and hardware versions are fixed from factory, and cannot be
changed by end-user or reseller.
This manual only covers products labelled with the product version (or range of versions)