8
Version No. V3R0
Safety Manual
9116 UniverSal converter
9 failure category
failure rates (1/h) for
RTD, TC, LinR and Potentiometer input, Current output
Fail Safe Detected
0.000E-0
Fail Safe Undetected
2.78E-07
Fail Dangerous Detected
3.52E-07
Fail Dangerous Undetected
4.30E-08
failure rates (1/h) for
RTD, TC, LinR and Potentiometer input, Relay output
Fail Safe Detected
0.000E-0
Fail Safe Undetected
3.59E-07
Fail Dangerous Detected
2.30E-07
Fail Dangerous Undetected
6.20E-08
failure rates (1/h) for
Voltage input, Current output
Fail Safe Detected
0.000E-0
Fail Safe Undetected
3.95E-07
Fail Dangerous Detected
4.79E-07
Fail Dangerous Undetected
5.60E-08
failure rates (1/h) for
Voltage input, Relay output
Fail Safe Detected
0.000E-0
Fail Safe Undetected
4.80E-07
Fail Dangerous Detected
3.53E-07
Fail Dangerous Undetected
7.60E-08
failure rates (1/h) for
Current input, Current output
Fail Safe Detected
0.000E-0
Fail Safe Undetected
4.44E-07
Fail Dangerous Detected
5.54E-07
Fail Dangerous Undetected
4.20E-08
failure rates (1/h) for
Current input, Relay output
Fail Safe Detected
0.000E-0
Fail Safe Undetected
6.36E-07
Fail Dangerous Detected
3.20E-07
Fail Dangerous Undetected
6.20E-08