Version No. V3R0
17
9116 Universal converter
safety Manual
14.2.1 If no password is set
action
Display shows
1
Press OK
ADV.SET
2
Set (ADV.SET) to Yes and press OK
SETUP
3
Set SETUP to SIL and press OK
EN.SIL
4
Set EN.SIL to YES and press OK
NEW.PAS
5
Set password to a number between 0 and
9999 and press OK
(At this time the device starts operating
in SIL mode with the entered configuration
parameters!)
CONFIG
Verify
OPEN->LOCK
(Note7)
6
Press OK to confirm verification of the OPEN-
>LOCK in the display
IN.TYPE
7
Verify input type and press OK
I.RANGE
8
Verify fixed input current range and press OK
(ONLY if IN.TYPE = CURR)
CONNEC
9
Verify sensor connection type and press OK
(ONLY if IN.TYPE = TEMP and SENSOR = Ni or Pt
or IN.TYPE = LIN.R)
UNIT
10
Verify temperature unit and press OK
(ONLY if IN.TYPE = TEMP)
SENSOR
11
Verify temperature sensor type and press OK
( ONLY if IN.TYPE = TEMP)
Pt.TYPE
12
Verify Pt sensor type and press OK
(ONLY if IN.TYPE = TEMP and SENSOR = Pt)
Ni.TYPE
13
Verify Ni sensor type and press OK
(ONLY if IN.TYPE = TEMP and SENSOR = Ni)
TC.TYPE
14
Verify Thermocouple type and press OK
(ONLY if IN.TYPE = TEMP and SENSOR = TC)
CJC
Note7: Open is shown briefly in the display.