Version No. V3R0
19
9116 Universal converter
safety Manual
Action
Display shows
29
Verify relay activation direction and press OK
(ONLY if REL.FUN = SETP)
HYST
30
Verify relay setpoint hysteresis and press OK
(ONLY if REL.FUN = SETP or WIND)
ERR.ACT
31
Verify relay action on sensor error and press OK
(ONLY if REL.FUN = SETP, WIND or ERR and the
selected input type and range support sensor error
detection, refer to section 4.3.2)
ON.DEL
32
Verify relay ON delay and press OK
(ONLY if REL.FUN = SETP or WIND)
OFF.DEL
33
Verify relay OFF delay and press OK
(ONLY if REL.FUN = SETP or WIND)
O.RANGE
34
Verify fixed output range for current output
OUT.ERR
35
Verify fixed output value on detected sensor error
and press OK
(ONLY if IN.TYPE
≠
VOLT, or IN.TYPE = CURR and
I.RANGE
≠
0-20 mA)
OUT.LO
36
Verify temperature for 0% output and press OK
(ONLY if IN.TYPE = TEMP)
OUT.HI
37
Verify temperature for 100% output and press OK
(ONLY if IN.TYPE = TEMP)
RESP
38
Verify analogue output response time and press OK CH1.CAL
39
Verify the use of applied process calibration values
and press OK
PASSW.
40
Verify password and press OK
SIL.OK
41
Verify SIL mode within 1 second