FM Installation drawing
For safe installation of 9202B the following must be observed. The module shall only be
installed by qualified personnel who are familiar with the national and international laws,
directives and standards that apply to this area.
For Installation in Zone 2 / Division 2 the following must be observed.
The 4501 programming module is to be used solely with PR electronics modules. It is
important that the module is undamaged and has not been altered or modified in any way.
Only 4501 modules free of dust and moisture shall be installed.
c-FM-us Certificate 3034430
U
o
/ Vt: 10.6 V
I
o
/ Isc: 12 mA
P
o
/P
t
: 32 mW
Lo/Ro La/Ra: 1150
H/
Group IIC
IIB
IIA
Group A,B
C,E,F D,G
C
o
/C
a
2.0
F 6.0
F 18
F
L
o.
/L
a
260 mH
780 mH 1000 mH
Terminal CH1(44,42) CH2(54,52)
U
m
: 253 V max. 400 Hz
Supply / Output
(terminal 11,12,13,14)
(terminal 31,32,33,34)
(terminal 91,92,93,94,95)
Non Hazardous area or
Class I, Division 2, Group A,B,C,D T4
or Class I, Zone 2 Group IIC T4
Hazardous area
Class I/II/III, Division 1, Group A,B,C,D,E,F,G
or Class I, Zone 0/1 Group IIC, [AEx ia] IIC or
or Class I, Zone 0/1 Group IIC, [Ex ia] IIC
Simple Apparatus or
Intrinsically safe apparatus
with entity parameters:
Vmax (Ui)
≥
Vt (Uo)
Imax (Ii)
≥
It (Io)
Pi
≥
Pt(Po)
Ca(Co)
≥
C
cable
+ Ci
La(Lo)
≥
L
cable
+ Li
-20
≤
Ta
≤
60ºC
44
43
42
41
54
53
52
51
34
33
32
31
14
13
12
11
9202
4501
91 92 93 94 95
Power
Rail
CH1
CH2
+
-
+
-
NA
MUR S
enso
r
Switch
S
w
itc
h w
. S
hu
nt
Co
nt
act Se
nso
r