9202 - Product Version 9202-003
27
9202QF01
LERBAKKEN 10, 8410 RØNDE DENMARK
Revision date:
2011-11-20
Version Revision
V4 R0
Prepared by:
PB
Page:
2/2
Terminal (31,32)
Supply:
Voltage
19.2 – 31.2 VDC
Power
max. 3 W
Terminal (33,34)
Status Relay:
Non Hazardous location: Division 2 or Zone 2 installation:
Voltage max.
125 VAC / 110 VDC
32 VAC / 32VDC
Power max.
62.5 VA / 32 W
16 VA / 32 W
Current max.
0.5 AAC / 0.3 ADC
0.5 AAC / 1 ADC
Terminal CH1(11,12) CH2(13,14)
Digital output:
NPN output:
Voltage max.
30 VDC
Current max.
80 mA
Terminal CH1(11,12) CH2(13,14)
Relay output:
Non Hazardous location:
Division 2 or Zone 2 installation:
Voltage max.
250 VAC / 30VDC
32 VAC / 30VDC
Power max.
500 VA / 60W
64 VA / 60 W
Current max.
2 AAC / 2ADC
2 AAC / 2 ADC
Installation notes:
The installation and wiring shall be in accordance with the Canadian Electrical Code for Canada and
National Electrical Code NFPA 70, Article 500 or 505 for installation in USA.
The module must be supplied from a Power Supply having double or reinforced insulation.
The use of stranded wires is not permitted for mains wiring except when wires are fitted with cable
ends.
For installation on the 9400 Power Rail the power must be supplied from Power Control Module Unit
9410.
Install in pollution degree 2, overvoltage category II.
The module must be installed in an enclosure suitable for the environment for which it is used.
For installation in Zone 2 or Division 2, the module must be installed in a suitable outer enclosure
according to the regulations in the CEC for Canada or NEC for USA.
The module is galvanically isolated and does not require grounding.
Use 60 / 75 ºC copper conductors with wire size AWG: (26-14).
Warning:
Substitution of components may impair intrinsic safety and / or suitability for Div. 2 / Zone 2.
Warning:
To prevent ignition of explosive atmospheres, disconnect power before servicing and do not
separate connectors when energized and an explosive gas mixture is present.
Warning:
Do not mount or remove modules from the Power Rail when an explosive gas mixture is
present.