UL cONTROL DRAWING 5104QU01
Hazardous (classified) Location
Class I, Division 1, Group A,B,C,D
Class I , Zone 0 and 1, Group IIC
Class II, Division 1 Group E, F, G
Intrinsically safe apparatus
entity parameters:
Vmax. (Ui)
≥
Vt (Uo)
Imax. (Ii)
≥
It (Io)
Pi
≥
Po
Ca
≥
Ci
La
≥
Lcable + Li
The sum of capacitance and
inductance of cable and
intrinsic safe equipment must
be less or equal to Ca and La
Installation notes:
1) The maximum nonhazardous location voltage is 250VAC/DC.
2) The installation shall be in accordance with the National Electrical Code
NFPA 70, Articles 504 and 505.
3) The terminals of the two individual channels shall not be interconnected in any
way.
4) Install in Pollution degree 2 or better
5) Use 60 / 75 °C copper conductors with wire size AWG: (26 – 14).
6) Warning: Substitution of components may impair intrinsic safety.
5104B Associated apparatus parameters
CH1
Terminals 41 to 44
CH2
Terminals 51 to 54
Vt Uo)
28 V
It (Io)
93 mA
Po
0.65 W
IIC / grp. A,B IIB / grp. C IIA / grp.D
Ca (Co)
0.052
μ
F
0.44
μ
F
1.45
μ
F
La (Lo)
2.4 mH
12 mH
20 mH
Nonhazardous
Associated apparatus
Galvanically Isolated
+
-
V
+
-
+
-
T
44
43
42
41
CH1
+
-
V
+
-
+
-
V
54
53
52
51
CH2
T
+
-
T
+
-
5104B
24
11
12
13
14
33
31
21
22
23
V
m A
m A
m A
V
I +
V +
I +
V
m A
m A
m A
V
I +
V +
I +
+
+
Curr
ent input
Voltage input
2-wire
installation
2-wire
installation
3-wir
e
transmitter
2-wir
e
transmitter
Supply
Supply
24...230 V
AC &
24...230 VDC
I
Output
I
Output
V
Output
V
Output
I+V
Output
I+V
Output
Rev. AA 2003-02-12
5104V104-UK
15