5104V104-UK
7
REPEATER / POWER SUPPLY
PRetrans 5104
• 1- or 2-channel version
• 3- / 5-port 3.75 kVAC galvanic isolation
• Loop supply > 17.1 V
• 20 programmable measurement ranges
• Universal supply by AC or DC
Application
• Supply voltage and safety barrier for 2-wire transmitters mounted in a
hazardous area.
• Safety barrier for analogue current / voltage signals from hazardous area.
• 1 : 1 or signal conversion of analogue current / voltage signals.
Technical characteristics
• The 20 factory-calibrated measurement ranges in the 5104 can be selected
by the internal DIP-switches without the need for a recalibration. Special
measurement ranges can be delivered.
• PR5104 is based on microprocessor technology for gain and offset. The
analogue signal is transmitted at a response time of less than 25 ms.
• Inputs, outputs, and supply are floating and galvanically separated.
• The output can be connected either as an active current / voltage transmitter
or as a 2-wire transmitter.
mounting / installation
• Mounted vertically or horizontally on a DIN rail. By way of the 2-channel
ver sion up to 84 channels per metre can be mounted.
•
Nb:
5104B is recommended as Ex barrier for 5331D, 5333D, 5334B, 5343B,
6331B, 6333B, and 6334B.