background image

UNIK2E230 

V2

 

ENGLISH

 

ISUNIK2E230v2_GB_10_12.doc 

 

 

11 

 

 

 

When the automation is completely open, to start the closing manoeuvre give a radio or manual command and 
the control unit: 
- carries out a fixed one second pre-flash 

drives the two motors with a 2

nd

 motor delay as set on the DEL trimmer

  

- if a command is issued during closure, the control unit carries out a complete re-opening. 
- the closure terminates  when the limit switch or the  obstacle detection device  are triggered or the manoeuvre 
time has elapsed.  

5.6 

 “PEDESTRIAN OPENING” FUNCTION 

The pedestrian function can be assigned  with the professional learning to channel 2/3/4 of the remote control. 
With  a  “PEDESTRIAN  OPENING”  (“EDG”  terminal)  command  on  the  input,  the  control  unit  commands  an 
opening for the first leaf for a time of: 
-  5 seconds if no learning has been carried out, 
-  half of the course if a simplified learning has been carried out 
-  that set by the installer if a professional learning has been carried out. 
Closing is triggered by a manual command, or automatically if the automatic closing function is enabled. The complete 
opening  command  has  always  priority  over  the  pedestrian  opening,  therefore  if,  during  a  pedestrian  manoeuvre  a 
complete opening command is received, the control unit will command a complete opening of the automation.  

5.7 

TRIMMER “OBS” - “OBSTACLE SENSITIVITY” DETECTION  

The  “OBS”  TRIMMER  is  used  to  adjust  at  the  same  time  the  delay  time  of  intervention  after  an  obstacle  has 
been detected and the threshold of the counter-force against the operator necessary to trigger the intervention. 
Both the counter-force and the delay time increase when the trimmer is turned clockwise. The delay time 
can  be  adjusted  between  0.1  and  3  seconds.  This  function  is  useful  to  overcome  any  critical  points  of  the 
operator which cause a higher power absorption by the motor for a short time. 
 

EXAMPLE 

 

delay time about 0,1 sec. 

EXAMPLE 

 

delay time about 1,5 sec. 

EXAMPLE 

 

delay time about 3 sec. 

 
If the OBS trimmer is in the MAX position, the obstacle detection is disabled. 
 
If electric limit switches are present, the obstacle detector will provoke an inversion of the motion in closing 
and a 2 second inversion in opening. 
If there are no electric limit switches the obstacle detector provokes: 
- in closing an inversion of the motion unless it is in the last five seconds of the manoeuvre, where does a STOP 
- in opening an inversion of the motion for 2 seconds unless it is in the last five seconds of the manoeuvre, 
where does a STOP. 

5.8 

FLASHING LIGHT 

The control unit has two output terminals (LAMP) to command a low voltage flashing light. The light start flashing 1 
second before each opening manoeuvre and 1 second before each closing manoeuvre. 
If the dip-switch 5 is in the OFF position the power supply to the flashing light is continuous. Therefore the terminals 
must be connected to a low voltage flashing light with a built-in oscillating circuit (type FEBOLIF).  
If  the  dip-switch  5  is  in  the  ON  position  the  power  supply  is  intermittent  and  therefore  a  normal  lamp  without 
oscillating circuit can be connected (230VDC, Max 10W). During the closing manoeuvre, the flashing frequency 
is twice as fast as that during opening. 
The flashing light is only activated during movement. 

5.9 

GATE OPEN WARNING LIGHT 

If the safety device self-test is not used (DIP 8 “PTST” is OFF), the TX (terminal 10) acts as a GATE 
OPEN WARNING LIGHT. You can connect a 24V lamp (max. 3W) to terminals 10 (“+TX”) and 9 (“COMMON”) 
of the control unit. The status of the lamp is as follows: 
- If the access is closed the light is switched off 
- If the access is open or opening the lamp is alight with a fixed light 
- If the access is closing the lamp flashes 

5.10  SLOW-DOWN 

The  slow-down  function  allows  the  gate  to  apply  a  reduced  force  before  reaching  the  limit  stop.  The  speed  is 
reduced to about one third of the normal working speed. 
The  slow-down  function  can  be  enabled  or  not  during  the  Professional  Learning  procedure.  The  moment  in 
which the slow-down starts can be differentiated between the opening and the closure. 

Intelligent Security & Fire Ltd.

Summary of Contents for UNIK2E230

Page 1: ...it Prastel S p A declines any responsibility in the event current standards in the country of installation are not complied with The symbol CE conforms with European Directive R TTE 99 05CE ELECTRONIC CONTROL PANEL FOR TWO 230VAC MOTORS UNIK2E230 _ V2 COMPLETE UNIK2E230SK _ V2 WITHOUT BOX AND TRANSFORMER BOX IP 54 I n t e l l i g e n t S e c u r i t y F i r e L t d ...

Page 2: ...ERATION OF THE SAFETY DEVICES 8 5 3 TRIMMER FOR MOTOR SPEED 9 5 4 TRIMMER DEL DELAY BETWEEN MOTORS 9 5 5 TRIMMER PAU OPENING AND CLOSING OPERATING MODE 9 5 6 PEDESTRIAN OPENING FUNCTION 11 5 7 TRIMMER OBS OBSTACLE SENSITIVITY DETECTION 11 5 8 FLASHING LIGHT 11 5 9 GATE OPEN WARNING LIGHT 11 5 10 SLOW DOWN 11 5 11 ELECTRIC LOCK 12 5 12 COURTESY LIGHT 12 5 13 LOGICAL STOP STP INPUT 12 5 14 CONTROL U...

Page 3: ...ing a trimmer Customisable partial opening for pedestrian transit 0 to 60 stand by time adjustment via trimmer 0 1 to 3 0 obstacle detection triggering time adjustment via trimmer Initial settings using dip switches Signalling LEDs 8 Expansion for electric lock 12V 15W max optional board ELU with optional relay Expansion for courtesy light optional board LCU Built in 433MHz rolling code receiver w...

Page 4: ...mmended set the Force to 100 FOR trimmer completely clockwise do not use the slow down carry out the professional learning procedure do not use the obstacle detection trimmer OBS to MAX i During the learning with no electric limit switches present and with the obstacle detection disabled e g with hydraulic operators or else with no mechanical STOP strike plate present to define the manoeuvre times...

Page 5: ...UNIK2E230 V2 ENGLISH ISUNIK2E230v2_GB_10_12 doc 5 4 1 GENERAL DIAGRAM OF SETTINGS AND CONNECTIONS 30 31 32 33 34 I n t e l l i g e n t S e c u r i t y F i r e L t d ...

Page 6: ... Description DIP STAUS Operation 1 2 CH RAD See pag 8 OFF OFF Button 1 of the TX enabled OFF ON Button 2 of the TX enabled ON OFF Button 3 of the TX enabled ON ON Button 4 of the TX enabled 3 FAST See pag 10 OFF Rapid re closing disabled ON Rapid re closing enabled 4 STRIKE See pag 12 OFF Lock stroke disabled ON Lock stroke enabled 5 LAMP See pag 11 OFF Flashing light fixed ON Flashing light flash...

Page 7: ...t from 1 Control unit starts pedestrian opening Press P1 SET or button 1 of the remote control to stop pedestrian opening Press P1 SET or button 1 of the remote control NO YES only by wire Photocell PHO in closing must Press P2 RAD or button 2 of the remote control Opening slow down Pedestrian function Safety intervention in closing Safety intervention in opening The EDG safety in opening must Sto...

Page 8: ... press and release the RPA learning pushbutton also see the instructions of the TX used Carry out this operation 5 6 metres from the receiver the LED signals the activation Transmit by pressing one of the channel pushbuttons of the new transmitter to be enabled Enable all the new transmitters by pressing a pushbutton on each one of them The exit from the procedure occurs automatically 10 seconds a...

Page 9: ...unter clockwise the speed of the motor if 50 of the maximum speed With the trimmer at half travel the speed of the motor if 75 of the maximum speed ATTENTION Changing the setting of trimmer FOR requires repeating the learning procedure since the travel times and the slow down start times change EXAMPLE Force Speed 50 EXAMPLE Force Speed 75 EXAMPLE Force Speed 100 5 4 TRIMMER DEL DELAY BETWEEN MOTO...

Page 10: ...rimmer is turned fully counter clockwise with a 2 nd motor delay of 3 seconds for all the other positions of the DEL trimmer the opening terminates when the limit switch or the obstacle detection device are triggered the manoeuvre time has elapsed or there is a radio or manual command In the latter case the control unit disables the automatic closing and to restart the manoeuvre a further command ...

Page 11: ... sec If the OBS trimmer is in the MAX position the obstacle detection is disabled If electric limit switches are present the obstacle detector will provoke an inversion of the motion in closing and a 2 second inversion in opening If there are no electric limit switches the obstacle detector provokes in closing an inversion of the motion unless it is in the last five seconds of the manoeuvre where ...

Page 12: ... the red LED still flashes an authorised service centre should be contacted 6 SIGNALLING LED Yellow led SET flashes for 5 seconds when turned on to indicate that it is possible to enter the Professional or Simplified Learning modes lights up with a fixed light while Professional or Simplified Learning are carried out is turned off when the control unit functions normally Red led ER is turned off d...

Page 13: ...the current available for the accessories Control Unit Transformer Power Power absorbed by the control unit Power available for the accessories Voltage of the accessories Current available for the accessories UNIK2E230 20VA 6 4W 13 6W 24V 560mA The following table shows the average absorption of the most common Prastel VDS accessories Product Absorption Photocell FOTO30SDE couple TX RX 50 mA Photo...

Page 14: ... control The remote control has not been memorised or is broken or the battery is flat Check change the battery Carry out the remote control acknowledgement procedure The electrical limit switch activates but the motor does not stop The opening and closing limit switches have been exchanged An NO contact has been used instead of an NC Check the connections The gate moves then stops both in opening...

Page 15: ...r and by current legislation All installation maintenance repairs and cleaning operations must be documented This documentation must be preserved by the user and made available to the personnel responsible for the control WARNINGS FOR THE USER Read the instructions and enclosed documentation carefully The product must be used for the express purpose for which it was designed Any other use is consi...

Reviews: