Javelin D
Ɣ
Model PD644 Voltmeter
Instruction Manual
23
Setting the Relay Operation (
rely
)
This menu allows you to set up the operation of the relays:
1. Relay
action
a. Automatic reset only (non-latching)
b. Automatic plus manual reset at any time (non-latching)
c.
Latching (manual reset only)
d. Latching with Clear (manual reset only after alarm condi-
tion has cleared)
e. Alternation
control
(automatic
reset
only)
f.
Off (relay and status LED disabled)
2. Set
point
3. Reset
point
4. Fail-safe
operation
a. On
(enabled)
b. Off
(disabled)
5. Time
delay
a. On delay (0-199 seconds)
b. Off delay (0-199 seconds)
rLY1
rLY2
FLSF
rELY
dLAY
Act1
SEt1
rSt1
FLS1
FLS2
dLy1
dLY2
Same
Functions as
Relay 1
From Setup
Menu
Press
Enter/Ack
button to access any menu
Press
Menu
button to exit at any time
www.
GlobalTestSupply
.com
Find Quality Products Online at:
sales@GlobalTestSupply.com