P
RO
V
U
PD6210 Analog Input Batch Controller Instruction Manual
10
Safety Information
CAUTION
:
Read complete
instructions prior to installation and
operation of the controller.
WARNING
:
Risk of electric shock
or personal injury.
Warning!
Hazardous voltages exist within enclosure.
Installation and service should be performed
only by trained service personnel.
Installation
There is no need to remove the controller from its case to complete the installation, wiring, and
setup of the controller for most applications. Instructions are provided for changing the transmitter
power supply to output 5 or 10 VDC instead of 24 VDC on page 11.
Unpacking
Remove the controller from box. Inspect the packaging and contents for damage. Report
damages, if any, to the carrier.
If any part is missing or the controller malfunctions, please contact your supplier or the factory for
assistance.
Panel Mounting Instructions
•
Prepare a standard 1/8 DIN panel cutout – 3.622" x 1.772" (92 mm x 45 mm). Refer to Figure 1 for
more details.
•
Clearance: allow at least 6.0" (152 mm) behind the panel for wiring.
•
Panel thickness: 0.04" - 0.25" (1.0 mm - 6.4 mm).
Recommended minimum panel thickness to maintain Type 4X
rating: 0.06" (1.5 mm) steel panel, 0.16" (4.1 mm) plastic panel.
•
Remove the two mounting brackets provided with the controller (back-off the two screws so that there is
¼" (6.4 mm) or less through the bracket. Slide the bracket toward the front of the case and remove).
•
Insert controller into the panel cutout.
•
Install mounting brackets and tighten the screws against the panel. To achieve a proper seal, tighten
the mounting bracket screws evenly until
controller is snug to the panel along its short side. DO NOT OVER
TIGHTEN, as the rear of the panel may be damaged.
Figure 1: 1/8 DIN Panel Mounting
!
3.622" (92 mm)
1.772"
(45mm)
Panel Cutout
to DIN 43700
Square Corners to 0.060"
(1.5mm) Max Radius
A
B
Tolerances:
A: +0.032 (+0.8mm)
-0.000 (-0.0mm)
B: +0.024 (+0.6mm)
-0.000 (-0.0mm)