PD6210 Analog Input Batch Controller Instruction Manual
17
Basic Operation and Programming
The PD6210 is factory calibrated prior to shipment to read in
milliamps and volts depending on the input selection. The
calibration equipment is certified to NIST standards.
Overview
Most setup and programming is done through the front panel buttons.
Jumper J4 located inside the controller, behind the input signal connector, is used to select the excitation
voltage (24 V [
Default Setting
], 10 V or 5 V) which is supplied to the P+ and P- wiring terminals.
After power and input signal connections have been completed and verified, apply power to the controller.
Front Panel Buttons and Status LED Indicators
Button
Symbol
Description
LED Status
Menu
1-8
Relay 1 – 8 indicators
START
(Right arrow/F1)
R
Rate indicator
BATCH
(Up arrow/F2)
T
Batch Total indicator
STOP
(Enter/F3)
G T
Grand Total indicator
Note:
F4 is a digital input. Alarms 5-8
enabled when relay expansion
module is installed.
▲
Total overflow
indicator
M
Manual control relays
&/or analog output
Programming
•
Press the Menu button to enter or exit the Programming Mode at any time.
•
Press the Right arrow button to move to the next digit during digit
or decimal point programming.
•
Press or hold the Up arrow button to scroll through the menus,
decimal point or press or hold to increment the value of a digit.
•
Press the Enter button to access a menu or to accept a setting.
•
Press and hold the Menu button for three seconds to access the advanced features of the controller.