PD6210 Analog Input Batch Controller Instruction Manual
29
Time Base, Total Conversion Factor & Total Reset
The time base, total conversion factor, and total reset menus are located in the
Program
menu.
The total and grand total have their own independent settings. This means that one can be displaying the
value in gallons while the other displays in million gallons, liters, m
3
, etc.
Batch Start Mode (
mode
)
The batch controller may operate in manual or automatic mode. In manual mode, the controller operates
as defined in Controller Operation as described on page 18. In automatic mode, the batch process will
automatically begin after a completed batch. The time delay for the restart may be 0.1 to 999.9 seconds
(
t dly
). Automatic batch start will only occur after a successful batch. A manually stopped batch will
require a manual start to begin a new batch process.
Grand Total Reset
The grand total can be programmed for manual or automatic reset. In the automatic reset mode, a
programmable time delay is available to reset the grand total after the assigned preset is reached.
Non-Resettable Totalizer
The total and grand total can be password-protected to prevent unauthorized resets. The grand total can
be programmed as a non-resettable total, see page 40 for details.
Calibrating the Controller with External Source (
Cal
)
To scale the controller without a signal source, refer to
Scaling the Controller (
SCALE
) page 27.
The controller can be calibrated to display the process variable in engineering units by applying the
appropriate input signal and the corresponding display value.
The use of a calibrated signal source is strongly recommended to calibrate the controller.
Warm up the controller for at least 15 minutes before
performing calibration to ensure specified accuracy.