PD6210 Analog Input Batch Controller Instruction Manual
44
Function Keys Operation
During operation, the programmable function keys operate according to the way they have been
programmed in the
Advanced Features – User
menu. The following table shows the default setting for
each of the function keys.
Function Key/Button Default Setting Action
F1/START
Start
Start batch
F2/BATCH
preset
Change preset
F3/STOP
stop
Pause/stop batch
F4/Digital Input
Srtstp
Start/stop batch
F4 Operation
A digital input, F4, is standard on the meter. This digital input is programmed identically to function keys
F1, F2, and F3. The input is triggered with a contact closure to COM, or with an active low signal. During
operation, F4 operates according to the way is has been programmed in the
Advanced Features – User
menu.
Only STOP Operation Enabled if a Batch is Running.
During a batch process, the only function that can be performed is the
pause/stop functions of the STOP button; the default programming of the F3
key. No other functions, including min/max display, manual alarm reset, or
total reset, will function while a batch is running.
Advanced Setup and Calibration
Multi-Point Calibration & Scaling
The controller is set up at the factory for 2-point linear calibration. The number of points for multi-point
calibration/scaling is set up in the
Advanced
Features
menu. Up to 32 linearization points may be
selected. See page 46 for details.
Maximum/Minimum Readings
The max & min readings (peak & valley) reached by the process can be displayed either continuously or
momentary:
1. Display briefly by assigning to the digital inputs in the
User
menu.
2. Display continuously by assigning either display to max/min through the
Display
menu.
Changing the programming of the F1-F3 function keys will
disable the default batch operation of these keys, and is not
recommended for batch control applications.
Any of the digital inputs can be programmed to reset the max & min readings.
To display max/min readings continuously:
Assign either display to Max (
d Hi
), Min (
d Lo
), or toggle between Max and Min (
d HL
) every 10
seconds.
!
!
Note that changing default the
programming of the upper or
lower displays will interfere with
seeing the batch total (upper
display) or rate (lower display) of
the batch process.
!