PD6210 Analog Input Batch Controller Instruction Manual
51
Factory Defaults & User Settings
The following table shows the factory setting for the major programmable parameters on the controller.
Parameter
Display
Default Setting
Input type
Input
4-20 mA
Total
yes
Total enabled
Units
units
Rate / total / gr. total
mA / mA / mA
Rate decimal
point
ddd.ddd
3 Places
Total decimal
point
ddddd.d
1 Place
G. Total
decimal point
dddddd
0 Places
Function
Functn
Linear
Number of
points
No Pts
2
Programming
prog
Scale
Input 1
InP 1
4.000 mA
Display 1
Dis 1
4.000
Input 2
InP 2
20.000 mA
Display 2
Dis 2
20.000
Display line 1
Line 1
Display total
Display line 2
Line 2
Display rate and units
Display
intensity
d-Inty
8
Total time
base
T tb
Second
Total
conversion
factor
T CF
1.000
Batch mode
mode
Manual
Grand total
time base
GT tb
Second
Grand total
conversion
factor
T CF
1.000
Grand total
reset
T rst
Manual
Relay 1
assignment
Asign1
Total
Relay 2
assignment
Asign2
Total
Relay 2
preclose
preCls
No
Relay 3
assignment
Asign3
Rate
Relay 4
assignment
Asign4
Rate
Parameter
Display
Default Setting
Relay 1
action
Act 1
Automatic
Batch preset
Preset
100.0
Relay 2
action
Act 2
Automatic
Relay 2 set
point
Set 2
200.0
Relay 3
action
Act 3
Automatic
Relay 3 set
point
Set 3
3.000
Relay 3 reset
point
RSt 3
2.500
Relay 4
action
Act 4
Automatic
Relay 4 set
point
Set 4
4.000
Relay 4 reset
point
RSt 4
3.500
Fail-safe
relay 1
Fls 1
Off
Fail-safe
relay 2
Fls 2
Off
Fail-safe
relay 3
Fls 3
Off
Fail-safe
relay 4
Fls 4
Off
On delay
relay 1
On 1
0.0 sec
Off delay
relay 1
Off 1
0.0 sec
On delay
relay 2
On 2
0.0 sec
Off delay
relay 2
Off 2
0.0 sec
On delay
relay 3
On 3
0.0 sec
Off delay
relay 3
Off 3
0.0 sec
On delay
relay 4
On 4
0.0 sec
Off delay
relay 4
Off 4
0.0 sec
Loop break
relay 1
ignore
Ignore
Loop break
relay 2
ignore
Ignore