Model PD650 Large Display Process Meter
Instruction Manual
57
Set the display for alarm # (1,2,3 or 4) set point
The entire display will flash for three seconds. For
instructions see
Five Basic Digit/Display Setting
Instructions,
page 30.
070.00
then
170.00
then
120.00
final
125.00
Set the display for alarm # (1,2,3, or 4)
reset point
As soon as the set point for alarm # (1,2,3 or
4) has been programmed, the meter displays
the reset point for alarm # (1,2,3, or 4). This is
indicated by the alarm # (1, 2, 3, or 4) LED
and
R
(reset point) LED being illuminated.
The reset point is programmed in the same
fashion as the set point above.
Meter displaying alarm # 1 reset
point
Press
ENTER,
then press
ENTER
again when the
set points (
SetPtS
) function appears.
SEtPtS
Preset values for set points assigned to
total without offset
For set points that have been assigned to
total without offset during the
Setup
function,
the preset # (1,2,3, or 4) will be illuminated.
This indicates that the value for preset # (1, 2,
3, or 4) is being programmed.
Meter displaying preset # 1
Set the display for preset # (1,2,3, or 4)
The entire display will flash for three seconds. For
instructions see
Five Basic Digit/Display Setting
Instructions,
page 30.
070.00
then
170.00
then
120.00
final
125.00