background image

 

4.0   PRE-STARTUP INSPECTION 

 
 
 

4.1   Minimum Equipment Required For Startup And Troubleshooting 

 

Volt-Ohn Meter 

 

Clamp-On Ammeter 

 

Megohm Meter 

 

Torque Wrench – inch lbs 

 

Torque Wrench – foot lbs 

 

4.2   Mechanical System Checks 

4.2.1   Plumbing Connections Completed 

 

Inlet / Makeup water? 

 

Discharge / Outlet? 

 

Drain / Blowdown? 

 

Relief / Safety Valve discharge? 

4.2.2   Feedpumps / Circulating Pumps 

 

Pumps wired, connected and checked for proper rotation? 

 

Is the boiler filled to the proper level with water? 

4.2.3 System Flush 

 

Has the System been flushed? 

 

Has the unit been cleaned of all construction debris?  

4.2.4   Valves 

 

Are all valves in the proper open or closed positions? 

 

4.3   Electrical System Checks 

 
 

WARNING:

  All 

POWER

 supplying boiler should be off and locked out with the unit(s) main power switch(es) 

OFF

 and  

Locked out! 

 

       

    Inspect all components, external and internal, to assure that there has been no damage during shipment or  

installation  

 

    Remove one of the unit’s control circuit transformer primary fuses.  Then check the resistance phase-to-

phase for all three phases.  Make sure that there are no short circuits phase-to-phase or phase-to-ground. 

 

With a megger (500VDC minimum) check contactor load side terminals to ground.  If a reading of <1 megohm is 
obtained, consult the Factory

Replace the control transformer fuse which was previously removed. 
 

    Remove element access panel(s) and open doors to the electrical control panel(s).  Run an inspection of the 

tightness of all electrical connections (IE: at fuse lugs, power entrance lugs, contactors, heating elements). 
All branch circuit connections should be tightened to 40 – 50 inch lbs.  (actual value listed on components).  
Torque to avoid component damage from heat build-up. This tightness inspection is vital, because the vibration 
during shipment can often loosen electrical connections.  If this is not done, damage may occur to component 
parts when power is switched on, and those damaged parts will not be covered under the manufacturer’s 
Limited Warranty. 
 

NOTE:

  See Maintenance Section on rechecking the torque on these components after an initial break-in period.  

Typically one to two weeks after start-up and then at least annually

 

Summary of Contents for HWST

Page 1: ...Installation and Operating Instructions ELECTRIC HOT WATER STEAM BOILERS...

Page 2: ...injury or property damage Read this manual thoroughly and follow the instructions herein The PRECISION Boilers shall be installed according to the procedures detailed in this manual or the Precision...

Page 3: ...2 Operating Instructions 9 5 2 2 Electric Door Interlocks 9 5 2 4 120 Volt Power Source 9 5 2 6 Alarm and Reset Circuits 9 5 2 7 Sequencing of Element Circuits 9 6 0 SEQUENCE OF OPERATION 6 1 Activati...

Page 4: ...f the authorities having jurisdiction 1 3 Recommendations 1 3 1 Preventative Maintenance A Preventative Maintenance Schedule is provided as a recommendation for periodic equipment Inspections Recordin...

Page 5: ...rs are not suitable for placement on combustible flooring 2 4 2 Leave a permanent space for element removal opposite element access panels as shown on the Dimensional Drawing DD and 36 inches opposite...

Page 6: ...ors The unit is equipped with grounding lugs s inside the power panel s The grounding conductors must be installed and sized in accordance with NEC Article 424 14 The recommended size is noted in the...

Page 7: ...fuses Then check the resistance phase to phase for all three phases Make sure that there are no short circuits phase to phase or phase to ground With a megger 500VDC minimum check contactor load side...

Page 8: ...t during the first day of operation the affected element will not be energized allowing the hot water to drive the moisture out at a controlled rate 4 4 3 Removal of Moisture in Element method 2 An al...

Page 9: ...same margin as specified for high limits to be above the controller setting 5 2 Operating Instructions 5 2 1 With the unit s control power ON OFF or ON OFF PREHEAT switch OFF close the main power swi...

Page 10: ...tactor coil circuits 6 2 2 Proportional Step Controls 6 2 2 1 Step Control Sequence The controller senses the unit s water temperature either via 135 ohm device or thermistor or steam pressure either...

Page 11: ...int the step controller should bring on nominally one half of the steps An adjustable proportional band is provided on the controller sensor to enable tuning the unit to system demand 7 1 2 Solid Stat...

Page 12: ...cause an automatic inverse change of 1 F at the control point NOTE Refer to the applicable vendor literature provided on both the setpoint controls and step controls installed in your boiler 8 0 PREV...

Page 13: ...k torque on element flange bolts The acceptable torque range is 10 15 ft lbs CAUTION Do not over tighten elements 8 4 2 Remove and replace any leaking elements or element gaskets Inspect handhole and...

Page 14: ...ement gaskets should be replaced immediately upon leak detection 8 5 1 Adequately tag wire and then remove wires from defective elements 8 5 2 Remove element by removing the four 4 attachment nuts 8 5...

Reviews: