l
240 VAC 60 Hz models
o
Rated operating voltage range: 180 VAC - 264 VAC.
o
Frequency: 47- 65 Hz
o
15 amp individual branch circuit
Frame Grounding Requirement
For operator safety and to minimize electrostatic discharge conditions have a certified elec-
trician verify that the AC frame ground continuity to be a low resistance connection to the AC
distribution ground bar
CAUTION
: To avoid electrostatic discharge shock, make sure that there is AC
frame ground continuity.
Individual branch circuit requirement
(US and Canada installations)
Also each Precor treadmill must be connected to a separate 15 amp individual branch cir-
cuit outlet. That means that no other devices can be connected to the same circuit outlet
receptacle.
l
Individual branch circuit
: An individual branch circuit provides a hot conductor and
neutral conductor to a receptacle. The conductors must not be looped, "daisy-
chained", or connected to any other conductors or receptacles. The circuit must be
grounded according to NEC guidelines or local region electric codes.
CAUTION
: All NEC (National Electric Code) guidelines or local region electric
codes must be complied with.
Equipment Spacing Requirement
The minimum side to side spacing between treadmills is 23.6 in (0.6 m) and the minimum
front to back spacing is 79 in (2 m).
Contact Precor Customer Support at support@precor.com or 800.786.8404 with
any questions.
Page 15
2 General Information
Equipment Spacing Requirement