16
Packaged and Split Rooftop Ventilator
© 2021 Mitsubishi Electric US, Inc.
Premi
Sys
R410A Piping Design
1- Pipe
Refrigerant pipe for CITY MULTI
®
shall be made of
phosphorus deoxidized copper, and has two types.
• Type-O: Soft copper pipe (annealed copper pipe),
can be easily bent with human’s hands.
• Type-
1
⁄
2
H pipe: Hard copper pipe (straight pipe),
being stronger than Type-O pipe of the same radial
thickness.
The maximum operation pressure of R410A air
conditioner is 4.30 MPa [624psi]. The refrigerant piping
should ensure the safety under the maximum operation
pressure. Follow the recommended pipe size in the table
below or you shall follow the local industrial standard.
Pipes of radial thickness 0.7mm or less shall not be
used.
Copper Pipe Size and Radial Thickness for
R410A CITY MULTI®
Size (mm)
O.D.
Size
(in.)
O.D.
**Radial
Thickness
(mm)
**Radial
Thickness
(mils)
*Pipe Type
ø6.35
ø1
⁄
4
0.8
[32]
1 or 2
ø9.52
ø3
⁄
8
0.8
[32]
1 or 2
ø12.7
ø1
⁄
2
0.8
[32]
1 or 2
ø15.88
ø5
⁄
8
1.0
[40]
1 or 2
ø19.05
ø3
⁄
4
1.2
[48]
1 or 2
ø22.2
ø7
⁄
8
1.0
[40]
2
ø25.4
ø1
1.0
[40]
2
ø28.58
ø11
⁄
8
1.0
[40]
2
ø31.75
ø11
⁄
4
1.1
[44]
2
ø34.93
ø13
⁄
8
1.2
[48]
2
ø41.28
ø15
⁄
8
1.4
[56]
2
*Pipe Type:
1=ACR-Annealed
2=ACR-Drawn Temper
**The figures in the radial thickness column are based on the
Japanese standards and are provided only as a reference. Use
pipes that meet the local standards.
Split DX Piping Installation
Piping Design
Refrigerant Line Sizes
DOAS Unit
Refrigerant Line Connections (in.)
MPF-1-**-**-96-1
1
⁄2 liquid
11
⁄8 suction
1
MPF-1-**-**-144-1
1
⁄2 liquid
11
⁄8 suction
MPF-2-**-**-144-1
1
⁄2 liquid
11
⁄8 suction
MPF-2-**-**-192-1
5
⁄8 liquid
13
⁄8 suction
2
MPF-2-**-**-240-1
5
⁄8 liquid
13
⁄8 suction
2
1 Field supplied 11
⁄8” -
7
⁄8” OD coupling may be needed at
DOAS for installation.
2 Field supplied 13
⁄8” - 1
1
⁄8” OD coupling will be needed at
DOAS for installation.
Outdoor Unit Model
Refrigerant Line
Connections (in.)
DOAS
Model
PUHY-P96T/YKMU
1
⁄2 liquid
7
⁄8
suction
MPF-1
PUHY-P144T/YKMU
1
⁄2 liquid
11
⁄8 suction
MPF-1
PUHY-P144T/YKMU
1
⁄2 liquid
11
⁄8 suction
MPF-2
PUHY-P192T/YSKMU
5
⁄8 liquid
11
⁄8 suction
MPF-2
PUHY-P240T/YSKMU
5
⁄8 liquid
11
⁄8 suction
MPF-2
PUHY-EP96T/YNU
1
⁄2 liquid
7
⁄8
suction
MPF-1
PUHY-EP144T/YNU
1
⁄2 liquid
11
⁄8 suction
MPF-1
PUHY-EP144T/YNU
1
⁄2 liquid
11
⁄8 suction
MPF-2
PUHY-EP192T/Y(S)NU
(twinned model)
5
⁄8 liquid
11
⁄8 suction
MPF-2
PUHY-EP240T/Y(S)NU
(twinned model)
5
⁄8 liquid
11
⁄8 suction
MPF-2
TUHYE096(3/4)
AN40A(N/B)
1
⁄2 liquid
7
⁄8
suction
MPF-1
TUHYE144(3/4)
AN40A(N/B)
1
⁄2 liquid
11
⁄8 suction
MPF-1
TUHYE192(3/4)
BN40A(N/B)
(twinned model)
5
⁄8 liquid
11
⁄8 suction
MPF-2
TUHYE240(3/4)
BN40A(N/B)
(twinned model)
5
⁄8 liquid
11
⁄8 suction
MPF-2