background image

 

Safety precautions

 

Safety precautions 

 

 

                         

 

                          

115V~/60Hz AC

                         

 

                          

                         

 

                          

Summary of Contents for PFR70800M

Page 1: ...0 0 0 This product is for domestic use only Use care manual Important safeguards Service Manual CHEST FREEZER SUPER DESIGN MODEL PFR70800M...

Page 2: ...ent 1 2 Product code illumination and Series Introduction 2 3 Specifications 3 4 Safety precautions 4 5 Function Schedule 7 6 System Flow Chart 8 7 Circuit Diagram 9 8 Maintenance Service and Trouble...

Page 3: ...PFR7080M 198 Color White Power Supply V Hz 115 60 Rated Input Power W 90 Power Consumption kW h 24h 0 76 Net Weight kg 32 Gross Weight kg Unit Dimension D W H mm Packing Dimension D W H mm Container...

Page 4: ...Safety precautions Safety precautions 4 115V 60Hz AC...

Page 5: ...Safety precautions 5...

Page 6: ...Safety precautions 6...

Page 7: ...Function Schedule Function Schedule Energy efficiency Micro foam technology Low noise operation Thick insulation for energy efficiency 7...

Page 8: ...Flow Chart 1 Schematic diagram of System Flow Chart 2 Brief Description of System Flow Chart It is a direct cooling single system Freezer When the Freezer is just powered on the refrigerant flows in t...

Page 9: ...on the Freezer Brief Description of Control Principle It is a direct cooling single system Freezer with a small ice box a mechanical type of all the control is generally adopted The thermostat direct...

Page 10: ...ower NO Check and repair according to the section of the compessor doesn t work YES If compressor can run naturally and temperature raising of condenser is very low YES NO Refrigerant leak check and r...

Page 11: ...capacity insufficient NO Check and repair according to the section of Cooling capacity is insuffcient YES 1 The thermostat was set at the coldest position 2 The ambient temperature is very high or th...

Page 12: ...ing 3 Cooling capacity is insufficient Cooling capacity is insufficient Is the ambient YES temperature low than 16eC Check the therostat is correct YES NO Does the refrigerant leak siowly Adjust and i...

Page 13: ...he power source and power cord NO Repair YES YES Is the ambient temperature low than 16 YES Check the therostat is correct Adjust and instruct consumer how to use Does the control panel has 220V power...

Page 14: ...ssure difference is still greater after the compressor has just stopped running the refrigerant will flow for a certain time therefore this sound is a normal phenomenon 2 A click sound can often be he...

Page 15: ...ations and natures of troubles should be determined according to their respective features therefore experience in servicing is very important to troubleshooting Service technicians with rich experien...

Page 16: ...y a sound similar to water flowing this is the sound produced by the normal circulation of refrigerant within the evaporator In case only the gas flowing sound can be heard and there is no water flowi...

Page 17: ...sly due to a certain trouble With this method you can reject some suspicious troubles and finally make a correct judgment 7 Analysis of Troubles and Troubleshooting A Poor Refrigerating Effect The so...

Page 18: ...refrigerant has been charged the liquid refrigerant that cannot evaporates in the evaporator will return to the compressor and thus a phenomenon of liquid striking will occur The liquid refrigerant ev...

Page 19: ...vaporator regularly if you fail to do so the frost layer on the evaporator tubing will become thicker and thicker Heat conduction will be severely affected when the whole tubing is wrapped with a tran...

Page 20: ...refrigerant and seal the charging port B No Refrigerating The phenomenon that the compressor runs normally but no frost or only a little frost appears on the evaporator and the Freezer temperature doe...

Page 21: ...hese phenomena will appear intermittently sometimes the Freezer works well and sometimes not well In order to determine whether it is clogged with ice heat the suspicious points with hot water to make...

Page 22: ...ing with dirt 3 Troubles of Compressor a Breakage of gas suction and discharge valve blocks Analysis of Trouble The compressor works by means of the opening and closing of gas suction valve and discha...

Page 23: ...he system Analysis of Trouble The residual air in the system will circulate together with the refrigerant in the system The major symptoms caused by this residual air is higher gas discharge pressure...

Page 24: ...er supply c Abnormal thermal protection Analysis of Trouble The compressor current is within its normal range but the thermal protector actuates repeatedly Remedy Replace the thermal protector with a...

Page 25: ...he user for buying a stabilizer so as to step up the voltage thus normal operation can be achieved 3 Check the thermal relay to see whether its contacts are closed Analysis of Trouble The contacts of...

Page 26: ...enon is caused mostly by poor lubrication such ad insufficient quantity of lubricant clogging in the lubricant oil line or intermittent lubricant oil supply Dirt and other impurities in the lubricant...

Page 27: ...ted value the thermostat won t work thus the compressor runs continuously When the evaporation temperature in the system is too high the temperature sensing agent in the temperature sensor is also hot...

Page 28: ...nsively measure the resistance between the power cord plug and the case body with an avometer the reading will be zero 0 in the worst case the fuse will be blown Check the 3 prong outlet to see whethe...

Page 29: ...tion becomes weake or vanishes If the Freezer has not been levelly placed put a level meter on its top table and adjust the leveling screws on its legs In case noise occurs from the compressor strike...

Page 30: ...30...

Reviews: