51
Trimax Operation
Manual Reset Hard Lockouts
Code
Lockout Message
Description
E1
Failed Ignition
The burner failed to light after 5 ignition attempts.
E2
False Flame
A flame is being detected prior to ignition.
E3
High Boiler Temperature
Boiler temperature has reached 210°F [99ºC]
E5
Blower Speed
Blower is not at correct speed or speed signal is not being received
by control module.
E8
Flame Circuit Error
Flame circuit test failed.
E9
Gas Valve Circuit Error
Gas valve circuit test failed.
E13
Reset Limit Reached
Resets are limited to 5 every 15 minutes.
E15
Sensor Drift
Supply or return sensor reading has drifted.
E16
Supply Sensor Stuck
Supply sensor reading is not changing.
E17
Return Sensor Stuck
Return sensor reading is not changing.
E18
Sensor Failure
Supply or return sensor reading changed very rapidly.
E21
Internal Control Fault
A / D conversion error.
E30
Supply Sensor Shorted
A short circuit has been detected in the boiler supply temperature
sensor circuit.
E31
Supply Sensor Open
An open circuit has been detected in the boiler supply temperature
sensor circuit.
E43
Return Sensor Shorted
A short circuit has been detected in the boiler return temperature
sensor circuit.
E44
Return Sensor Open
An open circuit has been detected in the boiler return temperature
sensor circuit.
E80
Return > Supply
Return temperature is higher than supply temperature.
E87
External Limit Open
An external manual reset limit has opened