SECTION 06B: ELECTRICAL
5
Circuit 21A shorted to ground
L70 low resistance value
MID 188 PSID # 125 Center Flash RH (A50 J1:7)
Type of
fault:
FMI
Description:
Fault Condition:
Possible
Symptoms:
Possible Causes:
FMI 3
Shorted High Voltage present on
output A50 J1:7 but
output not active
L68 always ON
A50 module failure
Connector C58 corroded
Connector C21 corroded
Circuit 23A shorted to battery
FMI 4
Shorted Low
Output A50 J1:7
shorted to ground
L68 not
working
A50 module failure
Connector C58 corroded
Connector C21 corroded
Circuit 23A shorted to ground
FMI 6
Current
above normal
Output A50 J1:7
internal software fuse
active for overcurrent
L68 not
working
A50 module failure
Connector C58 corroded
Connector C21 corroded
Circuit 23A shorted to ground
L68 low resistance value
MID 188 PSID # 27 Center Mkr (A50 J1:8)
Type of
fault:
FMI
Description:
Fault Condition:
Possible
Symptoms:
Possible Causes:
FMI 3
Shorted High Voltage present on
output A50 J1:8 but
output not active
L67 and L69
always ON
A50 module failure
Connector C21 corroded
Connector C58 corroded
Connector C15 Corroded
Circuit 46B shorted to battery
FMI 4
Shorted Low
Output A50 J1:8
shorted to ground
L67 and L69
not working
A50 module failure
Connector C21 corroded
Connector C58 corroded
Connector C15 Corroded
Circuit 46B shorted to ground
FMI 5
Open Circuit
A50 module does not
detect L67, L68, L69
or L70
L67 and L69
not working
A50 module failure
L67, L68, L69 or L70 open
circuit
Circuit 46B open
FMI 6
Current
above normal
Output A50 J1:8
internal software fuse
active for overcurrent
L67 and L69
not working
A50 module failure
Connector C21 corroded
Connector C58 corroded
Connector C15 Corroded
Circuit 46B shorted to ground
L67 or L69 low resistance
value
MID 188 PSID # 41 Cond Rly spd1 (A54 J1:5)
Type of
fault:
FMI
Description:
Fault Condition:
Possible
Symptoms:
Possible Causes:
FMI 3
Shorted High Voltage present on
output A54 J1:5 but
output not active
Condenser
fans always ON
speed 1
A54 module failure
Cond Power Relay R10 failure
Circuit 67A shorted to battery
Summary of Contents for X3-45 2016
Page 4: ......
Page 16: ...Section 00 GENERAL INFORMATION PA1593 12 FIGURE 12 METRIC US STANDARD CONVERSION TABLE 00005...
Page 17: ...Section 00 GENERAL INFORMATION 13 PA1593 FIGURE 13 CONVERSION CHART 00006...
Page 18: ......
Page 26: ......
Page 58: ......
Page 72: ...Section 04 EXHAUST AND AFTERTREATMENT SYSTEM PA1593 14 7 TORQUE SPECIFICATIONS...
Page 73: ...SECTION 04 EXHAUST AND AFTERTREATMENT SYSTEM PA1593 15...
Page 74: ...Section 04 EXHAUST AND AFTERTREATMENT SYSTEM PA1593 16...
Page 76: ......
Page 96: ......
Page 134: ......
Page 176: ...SECTION 06B ELECTRICAL 38 overcurrent working Circuit 306 shorted to ground...
Page 180: ......
Page 202: ......
Page 205: ...Section 09 PROPELLER SHAFT PA1593 3 FIGURE 1 PROPELLER SHAFT ASSEMBLY 09002...
Page 256: ......
Page 268: ......
Page 295: ...SECTION 16 SUSPENSION PA1593 9 2 5 TORQUE SPECIFICATIONS...
Page 296: ...Section 16 SUSPENSION PA1593 10...
Page 297: ...Section 16 SUSPENSION PA1593 11...
Page 314: ......
Page 380: ......
Page 388: ......
Page 413: ...Section 22 HEATING AND AIR CONDITIONING PA1593 15 FIGURE 18 REFRIGERANT CIRCUIT CENTRAL SYSTEM...
Page 433: ...Section 22 HEATING AND AIR CONDITIONING PA1593 35 FIGURE 36 CENTRAL HEATING SYSTEM COMPONENTS...