AIx<=00000
Determines if a LOW level on Analog Input x (x=1,2,..8) causes a call to be
placed. If this unit is a remote, then a call will be placed to the host. If this
unit is a host then a call will be placed to the remote that corresponds to this
input channel.
A LOW level occurs when the input value falls below this parameter. When
the input level rises above 2% above this parameter the level is considered
NORMAL and another call will be placed automatically.
Allowable values
: 00000 = no call on LOW level, 00001-65535 = call on LOW
level and call when HIGH level returns to NORMAL
The parameter is
calculated as follows:
[AI % CHANGE DIALING]
AIx%CHG=00000
Determines if a specific amount of change on Analog Input x (x=1,2,..8)
causes a call to be placed. If this unit is a remote, then a call will be placed to
the host. If this unit is a host then a call will be placed to the remote that
corresponds to this input channel.
The amount of change required before a call is placed is expressed as a
percentage of full-scale signal. Be aware that a full-scale signal is from 0-
20mA. Hence a 5% change would be 1mA. A call will be placed if the input
signal either rises or falls more than the specified percentage compared to the
signal level at the last call.
Allowable values
: 00000 = no call on HIGH level, 00001-65535 = call on
HIGH level and call when HIGH level returns to NORMAL
65535
20
)
(
×
=
mA
mA
SETPOINT
PARAMETER