..\Manuals\RCI-200-RF150 rev.B.doc
Page 4 of 15
RCI-200 Configuration:
The RCI-200 requires no configuration other than for its communication fail operation. In the event of a
communications failure on the communications board, the RCI-200 can be set up to take various
actions on its outputs. This may be desirable in order to place connected devices into a safe operating
mode. By default factory setting, all outputs remain at their last known state if a communications failure
occurs.
* If H1-3=IN then analog output #1 will ramp to the
setting of K1 and analog output #2 will ramp to the
setting of K2. Both outputs will change at a rate
determined by the setting of K3. The settings of the
trim pots can be read on test points TP
1,2,3
using a
voltmeter. The test points read a voltage of 0-5V for a
0-100% adjustment.
where,
Output
= 0-20 (mA) and
Ramp Rate
= 0-60 (seconds) (5 sec. minimum)
H1-
Function
OUT
IN
1
Relay Fail Mode
No Change
See H1-2
2
Relay Fail Status
De-Energize
Energize
3
Output Fail Mode
No Change
Ramp to K1/K2*
4
5
6
7
I/O Calibration
8
I/O Calibration
Volt
Output
TP
5
20
2
,
1
Volt
RampRate
TP
5
60
3