background image

..\Manuals\RCI-200-RF150 rev.B.doc 

                                                                                                          Page 2 of 15 

Inputs:

 

 
The  RCI-200  has  two  dry  contact  inputs  and  two  0-20mA  inputs.    The  dry 
contact  inputs  are  excited  with  24VDC  and  will  source  approximately  20mA 
when  the  contact  is  closed.    A  red  LED  lights  up  when  a  contact  input  is 
closed. 
 

 
The analog inputs are configured as 0-20mA inputs and have a 250

 input impedance.  

Each  input  terminal  has  three  connections:  +24V,  I/P,  COM.    The  +24V  power  output 
may  be  used  to  power  field  transmitters.    Up  to  500mA  may  be  used  to  power  a 
transmitter.  The input signal is connected to I/P(+) and COM(-). 
 
 

 
Analog inputs are connected to the RCI-800 in two fashions: 1) Normal (3-wire connection) or 2) two-
wire  connection.    On  a  3-wire  connected  input,  an  external  power  supply  or  the  +24V  power  output 
terminal of the RCI provides power to the field transmitter.  The field transmitter has a current source 
that  provides  the  4-20mA  signal  back to  the  RCI-800.    If  using the  power  supply  of  the  RCI-800,  the 
field transmitter may draw up to 125mA.  A total of 1A is available to power up to 8 field transmitters. 
 
On a 2-wire connected input, the field transmitter receives power from the RCI-800 and superimposes 
the signal onto the power return path.  A maximum of 20mA will flow in such a connection.  Make sure 
to consult the field transmitter manual to determine how to connect it to the RCI-800. 
 

 
 
 
 

Summary of Contents for RCI-200-RF150

Page 1: ...0 XXX If special or required 24 VDC 2 Dry Contacts and 2 Analog Inputs Input Remote Control Signal Interface XXX SER RS 232 485 Output 2 Form C Contacts and 2 Analog Outputs 117VAC 50 60Hz XXX RF9 900...

Page 2: ...ducts or all non standard products may not be returned for restocking Pribusin Inc warrants equipment of its own manufacture to be free from defects in material and workmanship under normal conditions...

Page 3: ...tion using License free 150MHz Radio Band 2 Watt selectable Radio Power Provides Reliable Communication 2 Dry Contact and 2 Analog Inputs 2 C Relay Contacts and 2 Analog Outputs Point to Point or Host...

Page 4: ...te 1 2 Analog 2 Contact 2 Analog 2 Contact Remote 2 Remote 3 Master to Multi Remote 2 Analog 2 Contact 2 Analog 2 Contact 2 Analog 2 Contact 2 Analog 2 Contact 12 25 10 25 6 5 www pribusin com info pr...

Page 5: ......

Page 6: ......

Page 7: ...a 125mA SLOBLO fuse It can be wired for 240VAC operation by removing de soldering power jumpers J1 J2 and installing soldering jumper J3 When changing the RCI 200 to 240VAC power make sure to change...

Page 8: ...g inputs are connected to the RCI 800 in two fashions 1 Normal 3 wire connection or 2 two wire connection On a 3 wire connected input an external power supply or the 24V power output terminal of the R...

Page 9: ...or from the inputs Care must be taken when connecting the outputs to different devices so that no inadvertent ground loops are established Output Calibration Input Testing The outputs on the RCI 200...

Page 10: ...communications failure occurs If H1 3 IN then analog output 1 will ramp to the setting of K1 and analog output 2 will ramp to the setting of K2 Both outputs will change at a rate determined by the se...

Page 11: ...may distinguish between them There may at most be as many remotes as there are inputs outputs on the host For example an RCI 200 having two analog contact inputs and outputs may communicate with up t...

Page 12: ...2 3 4 They are set as shown in the table SW2 5 SW2 6 Network ID OFF OFF 1 ON OFF 2 OFF ON 3 ON ON 4 SW2 HOST REMOTE 1 of Channels on each Remote of Channels on this Remote 2 of Channels on each Remote...

Page 13: ...quate for most applications If a longer timeout is required it may be set to 10 seconds SW1 6 Reply Timeout sec OFF 1 ON 10 RF Test Mode If the RF Test Mode is enabled the radio will send out a contin...

Page 14: ...s of the host using SW2 3 4 An RCI 200 can at most have 2 channels This is the number of channels that will be exchanged between the host and each remote SW2 3 SW2 4 Channels on Host OFF OFF 1 ON OFF...

Page 15: ...in a system must have a unique address SW1 1 SW1 2 SW1 3 Remote Address OFF OFF OFF 1 ON OFF OFF 2 OFF ON OFF 3 ON ON OFF 4 OFF OFF ON 5 ON OFF ON 6 OFF ON ON 7 ON ON ON 8 Next set the number of chan...

Page 16: ...hannels 1 Interval 10 sec Remote Channels 1 Interval 10 sec Number of Remotes 1 MURS Channel 1 Address 1 MURS Channel 1 Channels on Remotes 1 Power 1 Watt Power 1 Watt RCI 200 Host RCI 200 Remote Host...

Page 17: ...RCI 800 Host communicating with an RCI 800 Remote RCI 800 Host RCI 800 Remote Host Channels 8 Interval 10 sec Remote Channels 8 Interval 10 sec Number of Remotes 1 MURS Channel 1 Address 1 MURS Chann...

Page 18: ...RCI 200 Host RCI 100 Remote 1 RCI 100 Remote 2 Host Channels 2 Number of Remotes 2 Channels on Remotes 1 MURS Channel 1 Power 1 Watt Remote Channels 1 Address 1 MURS Channel 1 Power 1 Watt Remote Cha...

Page 19: ...MURS Channel 1 Power 2 Watt Remote Channels 4 Address 1 Interrogation 30 sec MURS Channel 1 Power 2 Watt Remote Channels 4 Address 2 Interrogation 30 sec MURS Channel 1 Power 2 Watt RCI 800 Host Host...

Page 20: ...It is desirable to operate with the highest signal strength achievable If the signal strength is less than 90dBm it is advisable to try to make adjustments to the system to bring the signal strength...

Page 21: ...ng installed We recommend coaxial cables be kept as short as possible and not exceed 100ft In some cases a direct line of sight may not be established but if there are solid structures such as buildin...

Reviews: