GTIB-30 Installation Manual-UL
52
4411-0011, Rev 2.0
The polarity of the input is not important. Maximum current drawn by each input at
24V is 60mA while the expected current consumption is below 20mA.
The digital input parameters of the optional GTIB-30 Client I/O device are
summarized in Table 8.
Table 8: Digital Input parameters of GTIB-30 Client I/O device.
Input High
24V
Input Low
0V
Maximum current drawn (at 24V)
60mA
Expected current drawn (at 24V)
<20mA
Polarity
Either
The input signals must be wired as indicated in the digital input connectors on the
optional GTIB-30 Client I/O device. Refer to Figure 30 for connector locations, Table 9
for connector descriptions, and to Figure 31 for the connector pin out diagram.
Table 9: Digital input connectors on optional GTIB-30 Client I/O device.
Description
Connector
Digital input assigned to digital output 1 IO1
Digital input assigned to digital output 2 IO2
Digital input assigned to digital output 3 IO3
The pinouts for these three connectors are identical and are shown in Figure 31.
INP
U
T
INP
U
T
NC
C
O
M
M
ON
NO
1 2 3 4 5
Figure 31: Digital input connector pin outs
Please contact PPS for assistance in configuring specific functions for these digital
inputs.
Pin 1 Input
Pin 2 Input
Pin 3 NC
Pin 4 Common
Pin 5 NC
Summary of Contents for GTIB-30
Page 1: ...Clean power made simple GTIB 30 Installation Manual ...
Page 2: ...www princetonpower com 4411 0011 Rev 2 0 April 1st 2014 ...
Page 11: ...About this Manual 4411 0011 Rev 2 0 xi This page intentionally left blank ...
Page 15: ...Contents 4411 0011 Rev 2 0 15 This page intentionally left blank ...
Page 16: ...1 Introduction ...
Page 18: ...2 System Overview and Configurations ...
Page 31: ...3 Pre Installation ...
Page 36: ...GTIB 30 Installation Manual UL 36 4411 0011 Rev 2 0 This page intentionally left blank ...
Page 37: ...4 Wiring Instructions ...
Page 56: ...GTIB 30 Installation Manual UL 56 4411 0011 Rev 2 0 This page intentionally left blank ...
Page 57: ...5 Commissioning Sequences ...
Page 61: ...GTIB 30 Installation Manual UL 4411 0011 Rev 2 0 61 This page intentionally left blank ...
Page 62: ...A GTIB 30 kW Specifications ...
Page 65: ...GTIB 30 Installation Manual UL 4411 0011 Rev 2 0 65 This page intentionally left blank ...
Page 66: ...B Return Material Authorization Contact and Product Information ...
Page 69: ...GTIB 30 Installation Manual UL 4411 0011 Rev 2 0 69 This page intentionally left blank ...