4.13.2 Digital Outputs
The GTIB-30 has up three dedicated digital outputs if the optional GTIB-30 Client
I/O device is installed.
The three digital outputs are realized via three SPDT relays on the optional GTIB-30
Client I/O device. A functional schematic of the SPDT relay is shown in Figure 32.
The switch position is controlled by the GTIB-30 via the coil. The user has access to
the normally open (NO), normally closed (NC) and the common (Common)
connection of the relays.
These relays are associated with the IO1, IO2, and IO3 connectors described in the
previous section.
Common
NC
NO
coil
Figure 32: Functional diagram of SPDT relay on optional GTIB-30 client input/output PCB
(** used for digital outputs)
The specifications of the relay contacts are provided in Table 10. Exceeding these
specifications will permanently damage the device and its components. Should
higher current rating be required, the built in relay can be configured to switch larger
external power relays.
Table 10: Digital output relay contact specifications of the optional GTIB-30 Client I/O device.
Rated Contact Current
1A
Rated Voltage
24VAC/DC
Breaking Capacity Max.
24VA
Summary of Contents for GTIB-30
Page 1: ...Clean power made simple GTIB 30 Installation Manual ...
Page 2: ...www princetonpower com 4411 0011 Rev 2 0 April 1st 2014 ...
Page 11: ...About this Manual 4411 0011 Rev 2 0 xi This page intentionally left blank ...
Page 15: ...Contents 4411 0011 Rev 2 0 15 This page intentionally left blank ...
Page 16: ...1 Introduction ...
Page 18: ...2 System Overview and Configurations ...
Page 31: ...3 Pre Installation ...
Page 36: ...GTIB 30 Installation Manual UL 36 4411 0011 Rev 2 0 This page intentionally left blank ...
Page 37: ...4 Wiring Instructions ...
Page 56: ...GTIB 30 Installation Manual UL 56 4411 0011 Rev 2 0 This page intentionally left blank ...
Page 57: ...5 Commissioning Sequences ...
Page 61: ...GTIB 30 Installation Manual UL 4411 0011 Rev 2 0 61 This page intentionally left blank ...
Page 62: ...A GTIB 30 kW Specifications ...
Page 65: ...GTIB 30 Installation Manual UL 4411 0011 Rev 2 0 65 This page intentionally left blank ...
Page 66: ...B Return Material Authorization Contact and Product Information ...
Page 69: ...GTIB 30 Installation Manual UL 4411 0011 Rev 2 0 69 This page intentionally left blank ...