GTIB-30 Installation Manual-UL
60
4411-0011, Rev 2.0
√
Item
Info
Measure and verify grid voltage in
range and frequency on grid side of
external grid disconnect
Only performed when grid is available
Close external grid disconnect
Only performed when grid is available
Measure grid voltage and frequency
in range and correct sequence inside
GTIB-30 on terminal blocks
Only performed when grid is available.
Open integrated DC disconnect
Open external DC disconnect
24V power supply inside GTIB-30 will
power down again if on previously.
Open external Grid disconnect
Wait 5 minutes for internal DC Bus
to discharge
Close external DC disconnect
Ensure integrated battery disconnect is open!
24 V PSU inside GTIB-30 will power up if
battery is sufficiently charged.
Close external Grid disconnect
Only performed if grid is available
Close integrated DC disconnect
Close integrated grid disconnect
Only necessary when grid connection
available. 24 V PSU in GTIB-30 will power
up if battery was insufficiently charged and
grid is available.
Close integrated control power
disconnect
HMI and other control systems should power
up.
Close and lock enclosure front door
Verify correct grid voltage and
frequency measurements on HMI
Refer to GTIB-30 user manual for HMI
operation.
Proceed with system configuration
via HMI as explained in user manual
System parameter configuration must be
performed before unit is turned on!
Summary of Contents for GTIB-30
Page 1: ...Clean power made simple GTIB 30 Installation Manual ...
Page 2: ...www princetonpower com 4411 0011 Rev 2 0 April 1st 2014 ...
Page 11: ...About this Manual 4411 0011 Rev 2 0 xi This page intentionally left blank ...
Page 15: ...Contents 4411 0011 Rev 2 0 15 This page intentionally left blank ...
Page 16: ...1 Introduction ...
Page 18: ...2 System Overview and Configurations ...
Page 31: ...3 Pre Installation ...
Page 36: ...GTIB 30 Installation Manual UL 36 4411 0011 Rev 2 0 This page intentionally left blank ...
Page 37: ...4 Wiring Instructions ...
Page 56: ...GTIB 30 Installation Manual UL 56 4411 0011 Rev 2 0 This page intentionally left blank ...
Page 57: ...5 Commissioning Sequences ...
Page 61: ...GTIB 30 Installation Manual UL 4411 0011 Rev 2 0 61 This page intentionally left blank ...
Page 62: ...A GTIB 30 kW Specifications ...
Page 65: ...GTIB 30 Installation Manual UL 4411 0011 Rev 2 0 65 This page intentionally left blank ...
Page 66: ...B Return Material Authorization Contact and Product Information ...
Page 69: ...GTIB 30 Installation Manual UL 4411 0011 Rev 2 0 69 This page intentionally left blank ...